CHECKING AND ADJUSTING THE INPUT
1. Follow steps 1 thru 6 of the OPERATING INSTRUCTIONS.

2. Attach a pressure gauge or a manometer to the manifold

pressure tapping and refer to table 10 for correct manifold

pressure.

3. Follow steps 7 thru 11 of the OPERATING INSTRUCTIONS.

4. Use this formula to “clock” the meter. Be sure that other gas

consuming appliances are not ON during this interval.

3600 x H = Btuh

T

Btuh = The approximate actual input rate.

T =

Time in seconds to burn one cubic foot of gas.

H =

Heating value of the fuel gas in Btu per cubic foot of gas.

EXAMPLE:

T = 9.0 seconds/ft

3

H = 1050 Btu/ft

3

(natural gas)

Btuh = ?

Gas flow through meter:

3600 x 1050 = 420,000 Btuh

9.0

Small changes in the input rate may be made by adjusting the

manifold pressure, see GAS PRESSURE REGULATORS. Under

no circumstances should you exceed the maximum input rate

for the boiler given in table 2 on page 6.

5. Repeat steps 1 thru 6 of the OPERATING INSTRUCTIONS.

6. Remove the pressure gauge or manometer from the manifold

pressure tapping. Replace the screw-in plug in the manifold

pressure tap.

7. Repeat steps 7 thru 11 of the OPERATING INSTRUCTIONS.

The boiler will resume normal operation.

When the boiler is operating at full capacity, or full gas input,

it should consume 1 cu. ft. of gas in approximately the time

indicated in table 10.

TABLE 10.

CONSUMPTION RATE

(Refer to Operating at Full Input or Full Capacity)

Type Gas

Heating

Value

Btu/Ft.

Time to Consume 1 cu. ft. of gas (seconds)

HW-

300

HW-

399

HW-

420

HW-

520

HW-

610

HW-

670

Natural

1050

12.6

9.5

9.0

7.3

6.2

5.7

Propane

2500

30.0

22.6

21.4

17.3

14.8

13.4

IMPORTANT

UNDER NO CIRCUMSTANCES SHOULD THE GAS INPUT

EXCEED THE INPUT SHOWN ON THE BOILER MODEL AND

RATING PLATE. OVERFIRING COULD RESULT IN DAMAGE

OR SOOTING OF THE BOILER. Minor variances from input

on rating plate can be corrected by adjustment of gas pressure

regulators described in GAS PRESSURE REGULATORS section

of this manual.

The inlet gas pressure must not exceed or be less than the values

shown on rating plate.