• In table 7 on page 21, select the row showing the distance to

the most remote outlet or the next longer distance if the table

does not give the exact length. This is the only distance used in

determining the size of any section of gas piping. If the gravity

factor is to be applied, the values in the selected row of table 7

are multiplied by the appropriate multiplier from table 8.

• Total the gas demands of all appliances on the piping system.

Enter table 7, on the left hand side, at the row equal to or just

exceeding the distance to the most remote outlet. Select the

pipe size in the row with a capacity equal to or just exceeding

the total gas demand. This is the required main gas supply line

size leading away from the gas meter or regulator. To determine

the pipe size required for each branch outlet leading away from

the main supply line, determine the gas demand for that outlet.

Enter table 7 on the same row, and select the branch pipe

size for a capacity equal to or just exceeding the demand at

that outlet. The main line can be resized for a lesser capacity

after each branch outlet, since the gas demand is reduced.

Total the gas demands of all remaining appliances branching

off downstream on the main gas line. Re-enter table 8 in the

same row and select the appropriate pipe size with adequate

capacity. Repeat the branch sizing and main line re-sizing for

any remaining appliances in the system.

EXAMPLE

Job Condition:

Determining the required gas pipe size for a system composed of two

HW-420 boilers and two HW-610 boilers to be installed as a multiple

group, 50 lineal feet from meter. Gas to be used has a .60 specific

gravity and heating value of 1,000 Btu per cubic foot.

Solution:

2 HW-420 Boilers

=

840,000 Btuh

2 HW-610 Boilers

=

1,220,000 Btuh

Total Btuh Input

=

2,060,000 Btuh

Total Btuh Input

=

2,060,000 Btuh = 2,060 cf/h

Btu per Cubic Foot of Gas 1,000

With a cubic foot per hour demand of 2,060 and with 50 lineal

feet of gas supply line, table 7 shows a pipe size of 3" (76mm)

is required.

NOTE: For other than .60 specific gravity, apply multiplier factor as

shown in table 8.

TABLE 8.

MULTIPLIERS TO BE USED WITH TABLE 7 WHEN APPLYING

THE GRAVITY FACTOR TO OTHER THAN .60 SPECIFIC GRAVITY

Specific

Gravity

Multiplier

Specific

Gravity

Multiplier

.35

1.31

1.00

.78

.40

1.23

1.10

.74

.45

1.16

1.20

.71

.50

1.10

1.30

.68

.55

1.04

1.40

.66

*.60 (Nat.)

1.00

*1.50 (Prop.)

.63

.65

.96

1.60

.61

.70

.93

1.70

.59

.75

.90

1.80

.58

.80

.87

1.90

.56

.85

.84

*2.00 (Butane)

.55

.90

.82

2.10

.54

*Use these correction factors if exact specific gravity of the gas is not known.

GAS PRESSURE REGULATORS
The gas pressure regulator is included in the combination gas valve,

Figure 15, and is set to operate on the gas specified on the boiler

model and rating plate.

GROUND

TERMINALS (2)

PILOT

OUTLET

GAS

CONTROL

PILOT ADJUSTMENT

(UNDER CAP SCREW)

PILOT SUPPLY

OUTLET

INLET

GAS VALVE KNOB

PRESSURE REGULATOR

ADJUSTMENT

PILOT ADJUSTMENT

UNDER SCREW

FIGURE 15.

Periodically check main burner, Figure 34 on page 39, and pilot

flame, Figure 35 on page 40, for proper operation. This should

be checked every six months.

Do not subject the gas valve to inlet gas pressures of more than 14"

W.C. (1/2 P.S.I.). If higher gas pressures are encountered, a service

regulator is necessary.

TABLE 9.

CORRECT MANIFOLD PRESSURE FOR FULL

BOILER INPUT (IN INCHES OF WATER COLUMN)

Model

Number

Rated

Input

Manifold Pressure

Natural

Propane

HW-300

300,000

3.5

10.0

HW-399

399,000

3.2

9.5

HW-420

420,000

3.5

10.0

HW-520

520,000

3.5

10.0

HW-610

610,000

3.5

10.0

HW-670 Nat.

660,000

3.5

HW-670 Prop.

670,000

10.0