TABLE 5, COMBINED VENT SIZING TABLES

MODEL HW-300 BOILER

Input: 300,000 Btuh

Draft Hood Outlet 8"

Required Connector or Smoke Pipe Diameter

Connector

Rise in Feet

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Connector Diameter (in Inches)

1

10

10

10

10

10

10

10

10

10

2

10

10

10

10

10

10

10

10

10

3

10

10

10

10

10

10

10

10

10

4 or more

Number

if Units

Combined

Total Input

Btuh x 1000

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Manifold and Common Vent Diameter (in Inches)

2

600

14

12

12

12

10

10

10

10

10

3

900

16

14

14

14

12

12

12

12

12

4

1200

18

16

16

14

14

14

14

12

12

MODEL HW-399 BOILER

Input: 399,000 Btuh

Draft Hood Outlet 10"

Required Connector or Smoke Pipe Diameter

Connector

Rise in Feet

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Connector Diameter (in Inches)

1

12

12

12

12

12

12

12

12

12

2

12

12

12

10

10

10

10

10

10

3

12

10

10

10

10

10

10

10

10

4 or more

10

10

10

10

10

10

10

10

10

Number

if Units

Combined

Total Input

Btuh x 1000

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Manifold and Common Vent Diameter (in Inches)

2

798

14

14

14

12

12

12

12

12

12

3

1197

18

16

16

14

14

14

14

14

12

4

1596

20

20

18

16

16

16

14

14

14

MODEL HW-420 BOILER

Input: 420,000 Btuh

Draft Hood Outlet 10"

Required Connector or Smoke Pipe Diameter

Connector

Rise in Feet

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Connector Diameter (in Inches)

1

12

12

12

12

12

12

12

12

12

2

12

12

12

10

10

10

10

10

10

3

12

10

10

10

10

10

10

10

10

4 or more

10

10

10

10

10

10

10

10

10

Number

if Units

Combined

Total Input

Btuh x 1000

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Manifold and Common Vent Diameter (in Inches)

2

840

14

14

14

12

12

12

12

12

12

3

1260

18

16

16

14

14

14

14

14

12

4

1680

20

20

18

16

16

16

14

14

14

MODEL HW-520 BOILER

Input: 520,000 Btuh

Draft Hood Outlet 10"

Required Connector or Smoke Pipe Diameter

Connector

Rise in Feet

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Connector Diameter (in Inches)

1

14

14

14

12

12

12

12

12

12

2

12

12

12

12

12

12

12

12

12

3

12

12

12

12

10

10

10

10

10

4 or more

12

12

12

12

10

10

10

10

10

Number

if Units

Combined

Total Input

Btuh x 1000

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Manifold and Common Vent Diameter (in Inches)

2

1040

16

16

14

14

14

14

12

12

12

3

1560

20

18

18

16

16

14

14

14

14

4

2080

22

22

20

18

18

18

16

16

14

5

2600

26

24

22

20

20

18

18

18

18

6

3120

28

26

24

22

22

20

20

18

18

7

3640

30

28

26

24

24

22

22

20

20

8

4160

32

30

28

26

24

24

22

22

20

MODEL HW-610 BOILER

Input: 610,000 Btuh

Draft Hood Outlet 12"

Required Connector or Smoke Pipe Diameter

Connector

Rise in Feet

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Connector Diameter (in Inches)

1

16

14

14

14

14

14

14

14

14

2

14

14

14

14

14

12

12

12

12

3

14

14

12

12

12

12

12

12

12

4 or more

12

12

12

12

12

12

12

12

12

Number

if Units

Combined

Total Input

Btuh x 1000

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Manifold and Common Vent Diameter (in Inches)

2

1220

18

18

16

16

14

14

14

14

14

3

1830

22

20

20

18

18

16

16

16

14

4

2440

26

24

22

20

20

18

18

18

16

5

3050

28

26

26

24

22

22

20

20

18

6

3660

32

28

28

26

24

24

22

22

20

7

4270

34

32

30

28

26

24

24

22

22

8

4880

36

34

32

30

28

26

26

24

24

9

5490

38

36

34

30

30

28

28

26

24

10

6100

40

38

36

32

30

30

28

26

26

11

6710

42

38

38

34

32

30

28

28

26

12

7320

44

42

38

36

34

32

32

30

28

MODEL HW-670 BOILER

Input: 660,000 or 670,000 Btuh

Draft Hood Outlet 12"

Required Connector or Smoke Pipe Diameter

Connector

Rise in Feet

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Connector Diameter (in Inches)

1

16

14

14

14

14

14

14

14

14

2

14

14

14

14

14

12

12

12

12

3

14

14

12

12

12

12

12

12

12

4 or more

12

12

12

12

12

12

12

12

12

Number

if Units

Combined

Total Input

Btuh x 1000

Total Vent Height (Measured in Feet Above Draft Hood)

10

15

20

30

40

50

60

80

100

Manifold and Common Vent Diameter (in Inches)

2

1220

18

18

16

16

14

14

14

14

14

3

1830

22

20

20

18

18

16

16

16

14

4

2440

26

24

22

20

20

18

18

18

16

5

3050

28

26

26

24

22

22

20

20

18

6

3660

32

28

28

26

24

24

22

22

20

7

4270

34

32

30

28

26

24

24

22

22

8

4880

36

34

32

30

28

26

26

24

24

9

5490

38

36

34

30

30

28

28

26

24

10

6100

40

38

36

32

30

30

28

26

26

11

6710

42

38

38

34

32

30

28

28

26

12

7320

46

44

40

38

36

34

34

32

30

Known:

(5) model HW-610 boilers. (See illustration).

Connector rise - 2' (Note 1' is minimum). Total vent

height 30'.

Problem:

Determine diameter of connector, manifold and

common vent.

Procedure: Enter the top of the HW-610 table (total vent height)

at 30' and the side at 2' (connector rise). A 14"

connector diameter is indicated for each connector

rise.

To determine the manifold and common vent size, enter table on this

page (total vent height) at 30 and the side at 5 boilers. A manifold

diameter of 24" (610 mm) is indicated.