FIGURE 28.

IMPORTANT

THE INSTALLATION OF SAFETY FLOW SWITCH AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF WATER SERVICE

INTERRUPTION OR CIRCULATOR FAILURE.

+ PIPING AND FITTINGS BETWEEN GATE VALVES AND BOILERS SHOULD BE BRASS OR BRONZE. OTHER PIPING SHOULD

CONFORM TO LOCAL CODES.

GATE VALVES ARE SHOWN FOR SERVICING BOILER. HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE.

*

PRESSURE RELIEF VALVE RATING SHOULD NOT EXCEED PRESSURE CAPACITY OF ANY COMPONENT IN THE SYSTEM.

** INSTALL THERMOMETER AND PRESSURE RELIEF IN OPENINGS PROVIDED ON HW-520, HW-610 & HW-670.

WIRING - FIGURES 16 and 17 on

pages 24 and 25.

INSTALL IN ACCORDANCE

WITH ALL LOCAL CODES

ONE HW-300, HW-399, HW-420, HW-520, HW-610 OR ONE HW-670 UP-FLOW MODEL

COMMERCIAL BOILER WITH VERTICAL TANK

USE THIS TABLE FOR CORRECT

PUMP AND WATER PIPE SIZE

Model

Number

Minimum

Pipe Size

(Inches)

B & G

Pump

Size

*Armstrong

Pump Size

HW-300

1-1/4"

125

S-25 1-1/4"

HW-399

1-1/2"

1-1/2" HV

H-32 1-1/2"

HW-420

1-1/2"

1-1/2" HV

H-32 1-1/2"

HW-520

1-1/2"

1-1/2" HV

H-32 1-1/2"

HW-610/670

2"

2"

S-35

* Assumes 50 equivalent feet of piping or less.

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE

TEMPERATURE AT FIXTURES. SEE TANK TEMPERATURE

CONTROL WARNING ON PAGE 11. IF HIGHER PREHEAT

TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE

BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT

WATER SUPPLIED TO FIXTURES.

PIPING