CHECKING HONEYWELL S-8600H OR S-8610M

INTERMITTENT IGNITION CONTROLS

Turn off gas supply.

Is voltage (24 Vac) across the 24 V terminals

on module during “Call for heat”?

Turn off power supply.

Is ignition cable firmly plugged into pilot

assembly and module?
Is ground wire firmly attached to pilot assembly and GND terminal

on module?

Ensure ground strap is the closest metal to the igniter/sensor

rod (electrode) to prevent the spark from shorting out to other

metal parts (pilot screen, pilot shield, etc.).

Ignition cable must not touch metal surfaces or current

carrying wires.
Is there a 1/8” gap between ground strap and electrode?

Is the ceramic insulator surrounding the electrode

cracked or broken?

Replace pilot burner assembly.

Replace ignition module.

Turn on gas supply.

Turn on power supply.

Securely connect cable

and/or ground wire.

Carefully bend downward

top of ground strap

to achieve 1/8”

spark gap.

Replace Ignition

Module.

YES

NO

YES

YES

NO

NO

NO

Is voltage (24 Vac) across the PV & MV/PV terminals on

“call for heat”?

YES

NO

NOTE: S8610M will automatically reset every 5 minutes. S8600H

pilot valve will be de-energized if module goes into lockout

condition. Reset system by turning electrical power off or by

turning system controller to off or down below "call for heat". Wait

one minute, then turn system on.

YES

Are ignition cable and ground wire in good condition

(not brittle, burnt or cracked)?

Replace pilot burner

and/or ground wire.

YES

NO

NO SPARK AT PILOT BURNER

YES