11 retransmission module, Retransmission module -29 – Yokogawa DA100 User Manual
Page 98

IM DA100-01E
4-29
4
Specifications
4.11 Retransmission Module
Style number: S10
Model code, number of output points, output signal, output range, terminal type
Model Number of Output Points Output Signal
Output Range
Terminal Type
DT500-11 10ch 1 to 5 VDC
0.8 to 5.4 VDC
screw
DT500-21 2ch 4 to 20 mADC
3.2 to 21.6 mADC
screw
Load resistance
DT500-11: 10 k
Ω or more
DT500-21: 600
Ω or less
Load capacitance
0.22 mF or less
Load Inductance
100 mH or less
Output accuracy (under reference operation conditions)* * *
±0.2% of Span
Calibration period
One year
Temperature coefficient
0.01% of Span/
°C
Highest resolution
DT500-11: 12 bit (approx. 1.43 mV)
DT500-21: 12 bit (approx. 5.86 mA)
Normal operating temperature/humidity
0 to 50
°C
20 to 80%RH for 0 to 40
°C and 10 to 50%RH for 40 to 50 °C (no condensation)
Update interval of output values
Same as the measurement interval
However, depending on the number of modules that are connected, the specified computational
expression, and the condition of the external storage medium, the output value may not be
updated at the measurement interval.
Output during SKIP
DT500-11; 0.05 V or less
DT500-21; 0.15 mA or less
Output filter
First order low pass filter in 10 levels (time constant in the range 4 ms to 3 s) can be applied to the
output value with respect to the changes in the measured data, computed data, and the
communication input value.
Insulation resistance
Across output terminals and ground: 20 M
Ω or more (500 VDC)
Withstand voltage
Across output terminals and ground: 500 VDC for 1 minute
Across channels
DT500-11: No insulation across channels (COM shared)
DT500-21: Insulation across channels (500 VDC, 1 minute)
Power consumption
Included in the value of the main unit or sub-unit.
Dimensions
Approximately 57(W)
×137(H) ×68(D) mm
Weight
DT500-11: Approximately 0.35 kg
DT500-21: Approximately 0.3 kg
Installation category (overvoltage category)
CAT II (IEC1010)