Extension cables, Connecting procedure – Yokogawa DA100 User Manual
Page 34

IM DA100-01E
2-13
2
Installation and Wiring
2.5 Connecting the Extension Cables (only for use
with the expandable type DA100)
Extension Cables
Any of the following extension cables can be used for connections between the DA100 main unit
and subunits or for connections between subunits.
Name
Model
Description
Extension cable
DV200-000
Length: 0.5m
Extension cable
DV200-001
Length: 1m
Extension cable
DV200-002
Length: 2m
Extension cable
DV200-005
Length: 5m
Extension cable
DV200-010
Length: 10m
Extension cable
DV200-020
Length: 20m
Extension cable
DV200-050
Length: 50m
Extension cable
DV200-100
Length: 100m
Extension cable
DV200-200
Length: 200m
Extension cable
DV200-300
Length: 300m
Extension cable
DV200-400
Length: 400m
Extension cable
DV200-500
Length: 500m
Connecting Procedure
Open the lid that covers the connector and insert the plug of the extension cable in the connector
until you hear a click. Since both connectors are identical, it makes no difference which connector
you use. Furthermore, since both plugs of the cable are identical, you may use either end.
When pulling the plug from the connector, gently press the peg of the plug and pull it forward.
Lid
Plug
Extension cable
Points to Note when Using the Extension Cables
· The maximum rated temperature is 60
°C;
· Never disconnect the extension cable from the connector by pulling the cable, since this might
damage the signal cable. Always hold the plug.
· When wiring the extension cable through a cable duct, or metal pipe or such, protect the peg on
top of the plug by covering it with tape.
· Fasten the cables in such a way that no force is being applied to connector or plug.
· To prevent the wire from snapping, etc. do no apply a pulling force of 70N or more. Furthermore,
do not bend the cable in a radius of 3 centimeters or less.
· For wiring conditions, refer to 2.9 Countering Noise.
Note
When several sub-units are connected, and the power is turned off of one of them, the other connected sub-
units which are further away from the main unit will not be recognized anymore.