Watlow Series SD Limit User Manual
Page 52

Wa t l o w S e r i e s S D L i m i t
■
5 0
■
A p p e n d i x
Electromechanical Relay, Form A
•
Minimum load current: 10 mA
•
Rated resistive: 2 A @ 240VÅ (ac) or 30VÎ (dc) maximum
•
Electrical life 100,000 cycles at rated current
•
For resistive loads only, must use RC suppression for inductive
loads
•
125 VA pilot duty, 120/240VÅ (ac)
Electromechanical Relay, Form C
•
Minimum load current: 10 mA
•
Rated resistive: 5 A @ 240VÅ (ac) or 30VÎ (dc) maximum
•
Electrical life 100,000 cycles at rated current
•
For resistive loads only, must use RC suppression for inductive
loads
•
125 VA pilot duty, 120/240VÅ (ac)
Process
•
Range selectable: 0 to 20 mA, 4 to 20 mA, 0 to 5VÎ (dc), 1 to
5VÎ (dc), 0 to 10VÎ (dc)
•
Reverse or direct acting
•
0 to 10VÎ (dc) voltage output into 1,000
Ω
minimum load resist-
ance
•
0 to 20 mA current output into 800
Ω
maximum load resistance
•
Resolution:
dc ranges: 2.5 mV nominal
mA ranges: 5 µA nominal
•
Calibration accuracy:
dc ranges: ±15 mV
mA ranges: ±30 µA
•
Temperature stability: 100 ppm/°C
Communications
EIA/TIA-485
•
Isolated
•
Modbus™ RTU protocol
•
9600, 19200 and 38400 baud rates
•
A maximum of 32 units can be connected (with additional 485
repeater hardware, up to 247 units may be connected)
•
Sampling rate: 20 Hz
Modbus™ is a trademark of AEG Schneider Automation.
IrDA
•
Modbus™ RTU via IRCOMM over IrDA
•
Sampling rate: 20 Hz
Agency Approvals
•
Factory Mutual Class 3545, Temperature Limit Switches. File
#3014848.
•
UL Listed Process Control UL3121
®
(UL 61010C-1), c-UL, CE,
IP65 (NEMA 4X), NEMA 12. File # E185611.
UL
®
is a registered trademark of the Underwriter’s Laborato-
ries, Inc.
•
CSA C22.2#24 Temperature Indicating and Regulating Equip-
ment. File LR30586.
•
NSF2 (National Sanitation Foundation) for calibration accuracy
with J, K, E, T, or RTD sensors. File 49660-0002-0001
Terminals
•
Touch-safe
•
Input power and control outputs: 12 to 22 AWG, 6 mm (0.25 in)
strip length
•
Sensor inputs and process outputs: 20 to 28 AWG, 8 mm (0.30 in)
strip length
•
Torque: terminal blocks 1 to 6 (SD _ _ - _ [C, K or J] _ _ - _ _ _ _)
and 1 to 4 (SD _ _ - _ F _ _ - _ _ _ _ ) are 0.8. Nm (7 in-lb);
terminal blocks 12, 13, 14 are 0.9 Nm (8 in-lb).
•
Solid or tinned wire recommended.
Power
•
100 to 240VÅ (ac) +10%; -15%; 50/60 Hz, ±5%
•
24V‡ (ac/dc) +10%; -15%; 50/60 Hz, ±5%; Class 2 power source
is required for low-voltage model.
•
10VA maximum power consumption
•
Data retention upon power failure via nonvolatile memory
Operating Environment
•
-18 to 65°C (0 to 149°F)
•
0 to 90% RH, non-condensing
•
Storage temperature: -40 to 85°C (-40 to 185°F)
Dimensions
Functionality Matrix
Note: These specifications are subject to change without prior
notice.
DIN Size
Behind
Panel
(max.)
Width
Height
1/32
97.8 mm
(3.85 in)
52.6 mm
(2.07 in)
29.7 mm
(1.17 in)
1/16
97.8 mm
(3.85 in)
52.1 mm
(2.05 in)
52.1 mm
(2.05 in)
1/8 Vertical
97.8 mm
(3.85 in)
52.8 mm
(2.08 in)
99.8 mm
(3.93 in)
1/8
Horizontal
97.8 mm
(3.85 in)
99.8 mm
(3.93 in)
52.8 mm
(2.08 in)
1/4
101.1 mm
(3.98 in)
99.8 mm
(3.93 in)
99.8 mm
(3.93 in)
Universal
Input
Limit
Alarm
Process 485 Comm
Input 1
Output 1
Output 2
Output 3