beautypg.com

Programming page example – Watlow Series SD Limit User Manual

Page 35

background image

Wa t l o w S e r i e s S D L i m i t

33

C h a p t e r 7 P r o g r a m m i n g

Programming Page Example

An oven manufacturer wants the user’s of their ovens to have easy access to the Series SD Limit parameters. They
also want to limit access to other parameters they do not want them to change. This can be achieved by customiz-
ing the Operations Page. The Programming Page configuration determines which parameters appear on the Opera-
tions Page. The Series SD Limit controller has 16 Programming Page locations, P1 to P16.

The oven manufacturer wants only these parameters to appear on the Operations Page:

• Fahrenheit/Celsius

• Alarm 2 Low Set Point

• Alarm 2 High Set Point

• Modbus

Address

To go to the Programming Page, press the Advance ‰ and RESET keys for six seconds from the Home Page.
{Prog} will appear in the upper display and {page} in the lower display.

Press the Advance Key ‰ to move through the parameter prompts.

Press the Up ¿ or Down ¯ keys to change the parameter value.

Press the Infinity Key ˆ at any time to return to the Home Page.

On the Programming Page, select the following settings:

[~C-F]

[A2;Lo]

[A2;Hi]

[Addr]

[none]

[none]

[~~P1]

[~~P2]

[~~P3]

[~~P4]

[~~P5] thru

[~P16]

To access the Operation Page parameters, press the RESET key to return to the Home Page. Press the Advance ‰
key to see the Operation Page parameters. Only the parameters selected on the Programming Page appear on the
Operations Page.

[~~~F]

[~~32]

[1000]

[~~~1}

[~C-F]

[A2;Lo]

[A2;Hi]

[Addr]