beautypg.com

Error messages – Watlow Series SD Limit User Manual

Page 50

background image

Wa t l o w S e r i e s S D L i m i t

4 8

C h a p t e r 9 F e a t u r e s

Indication

Probable Cause(s)

Corrective Action

[Er;In] Input error

The sensor may be improperly wired.

Sensor wiring may be reversed, shorted
or open.

The input may be set to the wrong sensor
or the controller may not be calibrated.

Calibration may have been corrupted.

Check sensor connections.

Check sensor connections and sensor
wiring.

Change Sensor Type

[`Sen] (Setup Page)

to

match the sensor hardware.

Restore factory calibration.

[Er;Ab] Ambient temperature error

Ambient temperature may be too hot or
too cold.

Calibration may be corrupted.

Verify that the temperature surrounding
the controller is 0 to 65°C (32 to 149°F).

Restore factory calibration.

[Er;CS] Checksum error

Settings may have changed unexpectedly.

Press the Reset Key to clear the error.

Verify settings. If error message persists,
contact the factory.

Error Messages