Wa t l o w S e r i e s S D L i m i t

36

C h a p t e r 8 F a c t o r y

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus

in parentheses.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

[``U;9]

[ V.9]

Input Calibrate, 9.0 Volt

Calibrate the process voltage input to 9.0
Volt (see “Calibrating the Series SD”).

[``no]
[`yes]

[``no]

*NA

Always active.

[``A;4]

[ A.4]

Input Calibrate, 4.0 mA

Calibrate the process current input to 4.0
mA (see “Calibrating the Series SD”).

[``no]
[`yes]

[``no]

*NA

Always active.

[`A;16]

[ A.16]

Input Calibrate, 16.0 mA

Calibrate the process current input to
16.0 mA (see “Calibrating the Series
SD”).

[``no]
[`yes]

[``no]

*NA

Always active.

[O3;1u]

[O3.1v]

Output 3 Calibrate, 1.0 Volt

The voltage process output transmits
1.000V (see “Calibrating the Series SD”).

[``no]
[`yes]

[``no]

*NA

The respective output is
process.

[O3;9u]

[O3.9v]

Output 3 Calibrate, 9.0 Volt

The voltage process output transmits
9.000 V (see “Calibrating the Series SD”).

[``no]
[`yes]

[``no]

*NA

The respective output is
process.

[O3;4A]

[O3.4A]

Output 3 Calibrate, 4.0 mA

The current process output transmits
4.000 mA (see “Calibrating the Series
SD”).

[``no]
[~yes]

[``no]

*NA

The respective output is
process.

[O3;16]

[O3.16]

Output 3 Calibrate, 16.0 mA

The current process output transmits
16.000 mA (see “Calibrating the Series
SD”).

[``no]
[`yes]

[``no]

*NA

The respective output is
process.

* The Series SD limit can be calibrated only with the front panel controls. These parameters are
not visible through serial communications.