Selecting an eia/tia-232 to eia/tia-485 converter – Watlow Series SD Limit User Manual
Page 19
Wa t l o w S e r i e s S D L i m i t
■
17
■
C h a p t e r 2 I n s t a l l a n d W i r e
When choosing an EIA/TIA 232 to 485 converter, look for
one with the following features:
Two-wire capability
EIA/TIA-485 can be implemented as a two-wire sys-
tem or a four-wire system. Most Watlow controllers,
including the Series SD limit, use two-wire commu-
nications when working with EIA/TIA-485. The con-
verter selected must have a two-wire mode. Some
converters can only be used in a four-wire mode.
Automatic Send Data control
In a two-wire system, both the transmitted signals
and the received signals travel over the same pair of
wires, so the converter must have a method of
changing from the transmit mode to the receive
mode. Some converters require the toggling of a con-
trol line (usually the RTS line) to perform this tran-
sition, while others use an automatic timing circuit.
The toggling method is dependent on the PC soft-
ware to toggle the control line and the PC’s operating
system to make that transition happen in a timely
manner. Because of these dependencies, the best
choice for a converter is one with automatic control.
Isolation
Converters are available with or without input-to-
output isolation. An isolated converter is not a re-
quirement when used with the Series SD, but it is
recommended to avoid ground loops. Also, isolation
could be a consideration when the Series SD will be
used on a network with other devices that may re-
quire isolation.
Power Supply
Many converters can be powered up either through
the signals of a serial port or through an external
power supply. Because some computers, such as lap-
tops, do not always provide enough power to supply
the converter, we recommend using an external pow-
er supply with specifications as recommended by the
converter manufacturer. Isolated converters may re-
quire two supplies.
Biasing and termination
If the system does not work properly, it may need
termination resistors at each end of the network. A
typical installation would require a 120-ohm resistor
across the transmit/receive terminals (3 and 4) of the
last controller in the network and the converter box.
Pull-up and pull-down resistors may be needed at
the converter to maintain the correct voltage during
the idle state. The pull-up resistor is connected be-
tween the positive of the DC supply and the T+/R+
terminal. The pull-down resistor is connected be-
tween the negative of the DC supply and the T-/R-
terminal.
Selecting an EIA/TIA-232 to EIA/TIA-485 Converter
Figure 17a — B&B Converter.
Isolated converter - 485OI9TB
Non-isolated converter - 485SD9TB
B&B Electronics Manufacturing Company,
(815) 433-5100, http://www.bb-elec.com/
Figure 17b — CMC Converter.
Non-isolated converter - ADA485L
CMC Connecticut Micro-Computer, Inc.,
1-800-426-2872, http://www.2cmc.com/
NOTE:
The CMC converter requires an external power supply when
used with a laptop computer.
Figure 17c — Wiring bias and termination resistors.
Controllers must be wired in a daisy chain configuration.
Add a 120
Ω
termination resistor on the last controller.
9VÎ (dc) (see note)
120VÅ (ac)
COM.
T+/R+
T-/R-
EIA-232
AD
A485L
EIA-485
A
B
A
B
G
9VÎ
G
DI/O
DI/O
3
4
7-ft. comms cable -
Watlow p/n 0219-0217-0000
T-/R-
TD (A)
TD (B)
T+/R+
120VÅ (ac)
Power
Supply
+
–
GND
4
3
485SD9TB
GND
12V
Î
(dc)
Watlow p/n 0830-0473-0002
Watlow p/n 0830-0473-0001
6 ft. comms cable -
Watlow p/n 0830-0473-0003