beautypg.com

Specifications, Specifications a.6 – Watlow Series 988LF User Manual

Page 60

background image

A.6

WATLOW Series 988LF Users Manual

Appendix

Specifications

Line Voltage/Power

• 100-240Vı(ac/dc) +10%, -15%; 50/60Hz, ±5%
• 24-28Vı(ac/dc) +10%, -15%; 50/60Hz, ±5%
• Power consumption 16VA maximum

Operating Environment

• 32 to 149°F (0 to 65°C)
• 0 to 90% RH, non-condensing

Storage Temperature

• -40 to 185°F (-40 to 85°C).

Agency Approvals

• UL, C-UL File # 43684
• CE: 89/336/EEC Electromagnetic Compatibility

Directive.
EN 50081-2: 1994 Emissions.
EN 50082-2: 1995 Immunity.

• 73/23/EEC Low-Voltage Directive.

EN 61010-1: 1993 Safety.

• NEMA 4X

Terminals

• #6 compression universal head screws (tighten

to 5 inch/pounds maximum), accepts 20-14
gauge wire.

Accuracy

• Calibration accuracy and sensor conformity:

±0.1% of span, ±1 LSD, 77°F ±5°F (25°C ±3°C)
ambient and rated line #voltage ±10%

• Accuracy span: 1000°F (540°C) minimum
• Temperature stability: ±0.2°F/°F (0.1°C/°C)

change in ambient

Mechanical

• 1⁄8 DIN panel mount, NEMA 4X (IP65

equivalent) front panel

• Overall width x height x depth
• Horizontal; 4.03" x 2.18" x 4.74", (102 mm x 55

mm x 120 mm)

• Vertical; 2.18" x 4.03" x 4.74", (55 mm x 102

mm x 120 mm)

• Depth behind panel; 4.06"(103 mm)
• Weight less than or equal to 14.0 oz (0.40kg)
I

nput Range

Specified temperature ranges represent the

controller's operational span.

Thermocouple

(Available with basic or universal signal

conditioner)

Type C

2

32

to

4200°F

or

0

to

2316°C

Type D

2

32

to

4200°F

or

0

to

2316°C

Type E

-328

to

1470°F

or -200

to

799°C

Type J

32

to

1500°F

or

0

to

816°C

Type K

-328

to

2500°F

or -200

to

1371°C

Type N

32

to

2372°F

or

0

to

1300°C

Type T

-328

to

750°F

or -200

to

399°C

Pt 2

2

32

to

2543°F

or

0

to

1395°C

(1064)

(Available with universal signal conditioner)

Type B

1598

to

3300°F

or

870

to

1816°C

Type R

32

to

3200°F

or

0

to

1760°C

Type S

32

to

3200°F

or

0

to

1760°C

RTD Resolution (DIN or JIS) (Avail. w/universal signal conditioner)

1° (DIN)

-328

to

1472°F

or -200

to

800°C

1° (JIS)

-328

to

1166°F

or -200

to

630°C

0.1° (DIN and JIS)

-99.9

to

999.9°F

or -73.3

to 537.7°C

Process (Available with universal signal conditioner)

0-50mVÎ(dc) -999 to 9999 units
0-5VÎ(dc)

-999

to

9999 units

1-5VÎ(dc)

-999

to

9999 units

0-10VÎ(dc)

-999

to

9999 units

0-20mAÎ(dc)

-999

to

9999 units

4-20mAÎ(dc)

-999

to

9999 units

Output Options

• Solid state relay, 0.5A @ 24V~ (ac) min., 253V~

(ac) max., opto isolated, burst fire. With or
without contact suppression.

• Open collector, switched dc signal provides a

minimum turn-on voltage of 3VÎ(dc) into a
minimum 500 load; maximum on voltage not
greater than 32VÎ(dc) into an infinite load,
isolated.

• Electromechanical relay

1

, Form C, 5A @ 120/

240~ (ac), 6A @ 28VÎ(dc), 1/8 hp. @ 120V~ (ac)
or 125VA @ 120V~ (ac). With or without contact
suppression. Off-state output impedance with
RC suppression is 20k .

• Process, 0-20mA (dc), 4-20mA (dc) into 800

maximum, 0-5VÎ(dc), 1-5VÎ(dc), or 0-10VÎ(dc)
into 1k minimum

1

, reverse acting, isolated.

1

Electromechanical relays are warranted for 100,000
closures only. Solid-state switching devices are
recommended for applications requiring fast cycle times or
extended service life.

2

Not an ANSI symbol.