Alarm type, Latching, Silencing – Watlow Series 988LF User Manual

Page 32: Sil] [`alt, Setup

background image

Setup

4.10

WATLOW Series 988LF Users Manual

Setup Menu, Chapter 4

[`SIL]

[`ALt]

Alarm Type

Selects the alarm type when Output 2 has been selected as an alarm.

• [``Pr] uses the process signal from input 1.

• [``de] uses a deviation from the input 1 signal.

[`ALt This prompt appears only on controllers equipped with output 2
hardware (not 98_L-___A-AA__). and with [`Ot2] set to [``AL] or [`ALn].

Default

[``Pr] [``de]

[`ALt]

[`ALt]

Latching

Select whether alarm for output 2 will be latching or non-latching. A
latching alarm [`LAt] must be turned off manually. A non-latching alarm
[`nLA] turns off when an alarm condition no longer exists.

[`LAt] This prompt appears only on controllers equipped with output 2
hardware (not 98_L-___A-AA__) and with [`Ot2] set to [``AL] or [`ALn].

Default

[`nLA]

[`LAt]

[`LAt]

[`LAt]

Silencing

Select silencing to inhibit alarm for Output 2 on startup and to allow
the operator to reset the alarm output, not the visual display.

• Silencing disables the alarm until the signal is between [A2LO] and

[`AHI].

[`AL2] This prompt appears only on controllers equipped with output 2
hardware (not 98_L-___A-AA__) and with [`Ot2] set to [``AL] or [[`ALn].

Default

[`OFF]

[``On]

[[`SIL]

[[`SIL]

[`LAt]