Range low 2 and range high 2, Rl2] [`rh2, Setup – Watlow Series 988LF User Manual
Page 29
Setup
Setup Menu, Chapter 4
WATLOW Series 988LF Users Manual
4.7
[`rSP]
Remote Set Point Input
continued from previous
page.
Range Low 2 and Range High 2
Select the low and high range for Remote Set Point Input. These
prompts limit the adjustment range for the set points. The default values
are the same as the limits of the sensor you selected by setting the input 2
DIP switch and selecting a value for Input 2 [`In2].
[`rL2] [`rH2] These prompts appear only on controllers equipped with
Remote Set Point Input hardware (98 _ L-_ 2__-AA__).
• Process inputs are scaled by these values. Range high is the value
displayed when the maximum process signal is present at the input.
Range low is the value displayed when the minimum process signal is
present at the input.
Example:
Set [`rSP] to [4-20]mA.
Set [`rL2] to [`100].
Set [`rH2] to [`500].
A 4mA input will display [`100].
A 12mA input will display [`300].
A 20mA input will display [`500].
• The low and high values of each sensor type are listed on the specifica-
tions page of the Appendix.
• Choose between Fahrenheit and Celsius at the [`C_F] prompt in the
Setup Menu.
[`rL2] [`rH2] These prompts appear only if the controller is equipped
with Remote Set Point Input hardware and with Remote Set Point Input
[`rSP] not set to [`OFF].
Default
DefaultDefault
Default
↓
↓
↓
↓
``°F]
[`°C]
[`rL2] [`rH2]
[`rL2] [`rH2]
[```J]
[``32]…[1500]
[```0]…`816]
98_L-1__-AA__ or
[`in2]
[`rL2] [`rH2]
[`rL2] [`rH2]
98_L-2__-AA__
[`rL2]
[`rH2]
[`rL2]
[`rH2]
Range Low 2 and Range
High 2 continued on next
page.
O
N
↑
1
2
3
O
N
↑
1
2
3
If
Default
↓
↓
RSP Input DIP
4-20mA 0-20mA 0-5VÎ
1-5VÎ 0-10VÎ(VDC)
[`OFF] [4-20] [0-20] [`0-5] [`1-5]
[0-10]
[`rSP]
[`rSP]
[`rSP]
[`rSP]
[`rSP]
[`rSP]
process
(Factory Preset)
RSP Input DIP
4-20mA 0-20mA 0-5VÎ
1-5VÎ 0-10VÎ(VDC)
[`OFF] [4-20] [0-20] [`0-5] [`1-5]
[0-10]
[`rSP]
[`rSP]
[`rSP]
[`rSP]
[`rSP]
[`rSP]]
mV process