32 ANASOFT User’s Guide
Loop Setup
Input type
The input types you can select depend on the type and options installed
in the controllers. The input types available are displayed in the input
type editing prompt. Input types available in Watlow-Anafaze
controllers include:
•
Thermocouple: Various types are available. The range is deter-
mined in firmware and by the Engineering Units selected.
•
RTD: Four ranges are available for the 100 ohm Platinum Element
DIN Curve RTD. The range is determined in firmware and by the
Engineering Units selected. See 7.0.1 & 7.0.3.
•
Linear: This is a linear voltage input type. it can be used with any
linear output sensor that can be scaled to the linear input voltage
range of the Watlow-Anafaze controller.
•
Pulse: This allows devices which generate digital pulse signals such
as optical encoders to be connected to the loop.
The table below describes the input types and ranges.
Input Type
F Range
C Range
J
-350 to 1400
-212 to 760
K
-450 to 2500
-268 to 1371
T
-450 to 750
-268 to 399
S
0 to 3200
-18 to 1760
R
0 to 3210
-18 to 1765
N
-450 to 2370
-268 to 1299
B
150 to 3200
66 to 1760
RTD 1
-148.0 to 572.0
-100.0 to 300.0
RTD 2
-184 to 1544
-120 to 840
RTD 3
-76 to 572
-60 to 300
Standard IR (IR 1)
-100 to 1600
-73 to 871
Heavy Duty IR (IR 2)
-100 to 1600
-73 to 871
Skip
loop is not scanned or displayed
Linear
See appendix B.
Pulse
0-2KHz