(2) Positioning is not Accurate





































(3) Abnormal Noise and Vibration are Generated

















YES

YES

YES

NO

NO

NO

YES

NO

Positioning is not accurate

Are the electronic

gear parameters

set properly?

Is the grounding wire

properly treated?

When the actuator is

stopped, does the current

value data of the PC

software indicate this fact?

Contact IAI.

Modify the parameter settings.

Perform proper grounding treatment.

Keep the wiring of the I/O cable sufficiently
distant from the power cable or shield the I/O
cable.
Check the pull-up resistance value if the
pulse-train output interface of the host
controller is an open collector.

Abnormal noise and vibration are

generated.

Are the parameter

settings appropriate?

Contact IAI.

Check the parameter settings.