3 configuring meter security, Using the front display – E-Mon E-PS-E-RTU-N User Manual
Page 92
Chapter 5 Configuring the PowerSmart+ PQM
Configuring Meter Security
92
PowerSmart+ Power Quality Meter
The available options are described in Table 17.
Table 17: Local Time Options
Display Label
Parameter
Options
Default
Description
Country
Country
Default, or country
name
Default
Defines calendar setting.
The default setting stands
for the U.S.A.
Daylight Saving Time Daylight Saving Time
Disabled, Enabled
Disabled When DST is disabled, the
RTC operates in standard
time only. When enabled,
the meter automatically
updates the time at the pre-
defined DST switch dates.
DST Start Month
DST Start Week of Month
DST Start Weekday
DST Start Month
DST Start Week
DST Start Weekday
Jan-Dec
Last, 1-4
Monday-Sunday
March
Last
Sunday
The date when Daylight
Saving Time begins.
DST Start Hour
DST Start Hour
1-6
2
The hour when Daylight
Saving Time begins.
DST End Month
DST End Week of Month
DST End Weekday
DST End Month
DST End Week
DST End Weekday
Jan-Dec
Last, 1-4
Monday-Sunday
March
Last
Sunday
The date when Daylight
Saving Time Ends.
DST End Hour
DST End Hour
1-6
2
The hour when Daylight
Saving Time begins.
Time Synchronization
Input
Time Synchronization Input
None
DI1 PPM – DI12 PPM
None
The external port receiving
the time synchronization
pulses
Daylight Saving Time
When the daylight saving time is enabled, the meter automatically
advances the device clock by one hour when daylight saving time begins
and puts the clock back one hour when it ends. The default daylight
saving time change points are preset for the U.S.A.
The daylight saving time option is disabled in the PowerSmart+ PQM by
default. If the daylight saving time option is disabled, you need to
manually adjust the device clock for daylight saving time.
Time Synchronization Pulses
External time synchronization pulses can be delivered through one of the
digital inputs.
If a digital input is selected as the time synchronization source, the edge
of an external pulse adjusts the device clock at the nearest whole minute.
The time accuracy could be affected by the debounce time of the digital
input, and by the operation delay of the external relay.
5.3 Configuring Meter Security
This setup allows changing the user password and enabling or disabling
password protection.
The password in your meter is preset to 0 at the factory, and password
protection is disabled.
Using the Front Display
Select the Password Setup entry from the Device Setup menu. See
Viewing and Changing Setup Options
in Chapter 3 for information on
configuring parameters via the front display.