E-Mon E-PS-E-RTU-N User Manual
Page 74

Chapter 5 Configuring the PowerSmart+ PQM
Configuring Communications
74
PowerSmart+ Power Quality Meter
The following table lists available client options.
Table 7: TCP Notification Client Setup Options
Parameter
Options
Default
Description
Client Enabled
NO, YES
NO
Enables operations of the
notification client
Server IP Address
192.168.0.3
The IP address of the notification
server
Server Port
0-65535
502
The TCP service port of the
notification server
Message Exchange
Address
0-65535
1000
The start address of a block
of 16 MODBUS registers for
receiving notification messages
Connections with a remote server are triggered via programmable
setpoints. To send event notifications to a server, configure a setpoint to
respond to desired triggers or to periodic time events and put the
"Notification" action to the setpoint action list (see
Configuring
Alarm/Control Setpoints
).
See the PowerSmart+ PQM Modbus Reference guide for more information
on operation of the notification client and the notification message
structure.