General Meter Setup
PowerSmart+ Power Quality Meter
77
In 4LN3, 3LN3 and 3BLN3 wiring modes, Min/Max volts, volt 
demands and voltage harmonics represent line-to-neutral 
voltages; otherwise, they will be line-to-line voltages. 
Transformer Correction
While using Highly accurate External CT meter option, transformer 
correction allows you to compensate ratio and phase angle inaccuracies of 
the user voltage and current instrument transformers. 
The following table lists available options.
Label
Parameter
Options
Default
Description
Ratio V1-V3
V1-V3
voltage
transformer 
ratio correction 
factor 
0.700 to 1.300
1.000
The ratio of the true 
transformer ratio to the 
marked ratio. 
Angle V1-V3 
 
V1-V3 
transformer 
phase 
angle
error, minutes
-600 to 600 
 
0
The phase 
displacement, in 
minutes, between the 
primary and secondary 
values. The phase angle 
of a voltage transformer 
is positive when the 
secondary value leads 
the primary value. 
Ratio I1-I3
I1-I3
current
transformer 
ratio correction 
factor 
0.700 to 1.300
1.000
The ratio of the true 
transformer ratio to the 
marked ratio. 
Angle I1-I3 
 
I1-I3 
transformer 
phase 
angle
error, minutes
-600 to 600 
 
0
The phase 
displacement, in 
minutes, between the 
primary and secondary 
values. The phase angle 
of a current transformer 
is positive when the 
secondary value leads 
the primary value. 