troubleShootIng

problem

probable cauSe SolutIon

Valve will not open. 1.

2.

Solenoids are inactive or

inoperative.

Foreign debris in

system.

1. Insert a fueling ticket into the Epson printer and start a

fueling.

2. Move the selector switch from RUN to STOP and back

to RUN. Listen for an audible clicking sound from the

solenoids.

3. If there is an audible click from the solenoid (but still no

flow), this may be an indication of a mechanical problem

with the main valve or its associated components.

Contact your local Liquid Controls distributor or the Liquid

Controls service department for assistance.

4. If there is no audible click from the solenoid, check the

voltage to pin #s 14, 15, 17 and 18 of terminal block J13.

While still in RUN mode, use a multimeter to measure

the following DC voltages on the circuit board. Use J8 pin

#38 as a ground.

TERMINAL # VoLTAGE
J13 #14 12.0VDC ±1.5VDC
J13 #15 1.0VDC ± 0.5VDC
J13 #17 12.0VDC ±1.5VDC
J13 #18 1.0VDC ±0.5VDC

5. If the above voltages are correct, this may be an

indication of a problem with the valve or its associated

components. Contact your local Liquid Controls

distributor or the Liquid Controls service department for

assistance.

6. If the above voltage are incorrect, replace the solenoids

(PN varies depending on system). If the valve problem

persists, replace the LCR 600 circuit board (PN 84040).