beautypg.com

Troubleshooting, Troubleshooting the lcr 600 – Liquid Controls FlightConnect 600 User Manual

Page 45

background image

45

troubleshooting the lcr 600

The troubleshooting section of this manual covers common problem situations. Call your local authorized Liquid

Controls service provider or the Liquid Controls electronics service department if the troubleshooting section does not

address the situation.

When troubleshooting the LCR 600 follow these guidelines:

• Check for proper operating voltages before changing the circuit board. If the circuit board needs to be changed, be sure to remove all

power to the LCR 600.

• The error message or a diagnostic ticket will contain an error message that can be useful in troubleshooting. Examine the diagnostic

screens on the LCR 600 or the diagnostic ticket to make sure all set-up fields are accurate, e.g. pulses per unit volume, temperature

coefficient and base temperature. Print a diagnostic ticket by moving the red selector switch to “SHIFT PRINT” for less than two

seconds.

• Never remove a terminal block or jumper with the power on.
• Never install a terminal block or jumper with the power on.
• Never force a terminal block into its location.
• Never exchange or reposition terminal blocks on the circuit board.
• In case of a major problem such as a burned or water-damaged circuit board, evaluate possible causes before replacing it and

turning the power back on.

• Isolate the problem before changing the circuit board.
• Return faulty circuit boards with the proper forms, concisely completed, to a LC service provider.

problem

probable cauSe

SolutIon

unit will not power

up or no display.

1. Inadequate supply

voltage. 9 to 28 VDC is

required for operation.

1. With the key in the accessory position, check the battery

voltage to the circuit board at J6. Use terminal #11 as

positive and terminal #12 as DC ground. While the LCR

600 will power-up at 9 VDC, it is recommended that the

input be at least 12.6 VDC. Voltage less than 12 VDC

may cause failures in equipment connected to the LCR

600, such as valves or external displays

2. Check the 7.5 A, in-line fuse (PN 70985) for continuity.

It is located on the accessory power line. Replace if

necessary.

unit blows 7.5 a

fuse.

1. 12 VDC Battery line is

shorted to ground.

1. For safety reasons, remove the 7.5 A in-line fuse from

the accessory power cable.

2. Remove the J6 terminal block. Inspect for stray wire

stands and visible shorts.

3. Using a multimeter, take a reading across terminal 11

and terminal 12 on the J6 terminal block. The terminals

should be open. If the multimeter shows a short, replace

the power cable (PN 81512).

4. Inspect the length of the power cable for damaged

insulation that could cause a short between the wire

and the chassis (or other nearby metal). If the cable is

damaged, replace it.

5. Replace the 7.5 A fuse (PN 70985) and re-install the J6

connector.

6. If the 7.5 A fuse blows again, replace the LCR 600 circuit

board.

troubleShootIng