dIagnoStIcS -

error meSSageS

PoWeR FAIL eRRoR

The fueling ended due to a loss of input voltage greater than 15 seconds. This message is displayed if power is

removed during a fueling. Ensure that power was not turned off manually, then check the power supply, the wiring and

the in-line fuse. See the troubleshooting section for more information. See page 45.

PReSeT eRRoR

When accessing a preset field, a flash memory error was detected. If this error persists, contact a LC service provider.

dATA ACCeSS eRRoR

A flash memory error occurred. If this error persists, contact a LC service provider.

INIT WARNING

This message appears when the

No-Flow Timer or the Ticket Required? field return an error. If this error

occurs, the fueling can continue but default values

180 and Yes are used. If this error persists, contact a LC service

provider.

run tIme error meSSageS

These messages may be displayed if an error occurs while the system is

running.

Invalid entry or value out of specified range

The value entered into the text box is outside of the range specified for

the field. Reenter the value.

FLASH CRC FAILURe

The CRC stored with an LCR 600 data block indicates the data or CRC

has been corrupted. A rebuild operation could possibly fix the problem.

If not, try a clear all (contact a LC service provider). If that does not

work, hardware may be at fault and the unit should be returned to Liquid

Controls for more analysis. Before starting a clear all operation, print a

calibration ticket.

FLASH WRITe FAILURe

A failure detected while a data block was being written to the flash memory. See Flash CRC Failure above for

corrective actions.

FLASH NoT INITIALIZed

The selector switch was not in the CALIBRATION position when a

Clear All or Rebuild was attempted.

Duplicate flow rates not allowed

This message only appears when setting up multi-point calibration. When calibrating a multi-point flowmeter, each

linearization point must have a unique flow rate. This message is displayed if a duplicate flow rate is entered.

Adjacent linearization points out of 0.25% range

This message only appears when setting up multi-point calibration. When calibrating a multi-point flowmeter, adjacent

linearization points must be within a 0.25% correction of each other. To avoid this error, select an additional flow rate

and correction factor between the two points. More than one additional point may be required.

Invalid logon parameters

flightconnect

The Fueler ID and/or password entered does not exist in FlightConnect’s Fueler database. Enter a valid Fueler ID.

Invalid parameter

flightconnect

A RUN command was issued and a required parameter (fueling detail) is missing. Enter the required parameter. Then,

FlightConnect will allow the fueling to start.

Invalid entry

flightconnect

The value entered does not meet the requirements of the field. This error often appears when a required field is left

blank. Enter the proper data.

There was no response from the LCP device.

flightconnect

The LCR 600 attempted to retrieve data from the office, but can not connect. Retry. If the error persists, check the

transmission device on the vehicle. If the error still persists, check the office computer and office transmission device.

If the problem still persists, make sure that DBManager and FlightConnect Read are running and configured properly.

S Y S T E M S E T U P

1

Meter ID:
Unit of Measure:

Decimal Digits:

Residual Processing:
Flow Rate Base:

A101

GALLONS

TENTHS

ROUND

PER MINUTE

d P S h u t d o w n V a l u e

250

LCP02SetField: 113

Invalid entry or value is out of

specified range.