Setup, Calibration setup – Liquid Controls FlightConnect 600 User Manual
Page 23

23
calIbratIon Setup
- Setup
calIbratIon Setup 2
Calibration #:
(LB)
c - u - l
flightconnect
The active calibration of 16 possible calibrations. The fields shown
on the Calibration Setup 2 screen represent the values of the
Calibration # shown. Any edits made to the fields are attributed to
the
Calibration # shown. FlightConnect only uses Calibration #1.
Compensation Type:
(LB)
c
The type of temperature volume compensation applied to the active
Calibration #. Refer to the Compensation Types and Parameters
table on page 27 to find the correct compensation. If
NoNe is selected,
fuelings will be in gross quantities only.
Linear F • Linear C • API Table 24 • API Table 54 • API Table 6B • API Table 54B •
API Table 54C • API Table 54D • NH3 • NONE
Compensation Parameter:
(tB)
c
The coefficient of expansion, the standard density, API gravity, or the specific gravity applied to the
Compensation
Type. This field has default values that are set when Compensation Type changes. Ensure the default value is
correct. Refer to the Compensation Types and Parameters table on page 27 for ranges.
Base Temperature:
(tB)
c
The base temperature for temperature compensated fuelings. Although this field is editable for some
Compensation
Type values, it defaults to 60°F or 15°C according to the selected Compensation Type.
Gross Quantity:
Display only
The gross volume of the latest calibration fueling.
Gross Preset:
(tB)
c - u - l - p
The gross preset for the next calibration fueling.
Temperature:
Display only
The current temperature reading of the RTD temperature probe.
Net Quantity:
Display only
The net volume of the latest calibration fueling.
Auxiliary Multiplier:
(tB)
c
The factor used to convert the measured volume of a fueling to an alternate volume or mass unit. If this field is 0, it will
not print on the fueling ticket. Users must furnish a conversion factor.
example
auxiliary multiplier = (Spgr) x (8.345 Ibs/gal)
SpGr = specific gravity
Auxiliary Quantity:
(tB)
c
The alternate volume or mass delivered using the
Auxiliary Multiplier.
Auxiliary Unit of Measure:
(LB)
c
The auxiliary unit of measure printed on the fueling ticket.
Gallons • Litres • Cubic M • LBS • KGS • Barrels • Other
Calibration #: 1
Compensation Type:
Comp Parameter:
Base Temperature:
Gross Quantity:
Gross Preset:
Temperature:
Net Quantity:
Auxiliary Mult:
Auxiliary Quantity:
Auxiliary Unit/Measure:
Gallons
None
----------
----
11.5 Gallons
0.0 Gallons
74.7
11.2
0.000
0
Litres
C A L I B R A T I O N S E T U P
Next/Previous Screen
2
l - locked
u - unlocked
c - Weights & measures calibration
p - Stop/pause
f - factory
Security clearance
The fields on the Calibration Setup 2 screen are used
to define temperature compensation parameters for
flowmeter systems with ETVC kits installed. Fields
should be left blank for systems without ETVC.
flightConnect & temperature Compensation