Ordering Information
Mfr. Part No.
Code
Description
3-8350-1
159 000 192
Temperature transmitter Field mount
3-8350-1P
159 000 193
Temperature transmitter Panel mount
3-8350-2
159 000 194
Temperature transmitter Field mount with relays
3-8350-2P
159 000 195
Temperature transmitter Panel mount with relays
3-8350-3
159 000 196
Temperature transmitter Field mount with dual input/output
3-8350-3P
159 000 197
Temperature transmitter Panel mount with dual input/output
Accessories
Mfr. Part No.
Code
Description
3-8050
159 000 184
Universal mounting kit
3-8052
159 000 188
3/4 in. Integral mounting kit
3-8052-1
159 000 755
3/4 in. NPT mount junction box
3-8050.395
159 000 186
Splashproof rear cover
3-8050.396
159 000 617
RC Filter kit (for relay use)
3-0000.596
159 000 641
Heavy duty wall mount bracket
3-5000.598
198 840 225
Surface Mount Bracket
3-9000.392
159 000 368
Liquid tight connector kit for rear cover (includes 3 connectors)
3-9000.392-1
159 000 839
Liquid tight connector kit, NPT (1 piece)
3-9000.392-2
159 000 841
Liquid tight connector kit, PG13.5 (1 piece)
3-9900.396
159 001 701
Angle Adjustment Adapter Kit
Display Condition
Possible Causes
Suggested Solutions
Check Sensor?
• Sensor not wired properly.
• Sensor connected to 8350 while power
is on.
• Defective sensor.
• Correct sensor wiring.
• Recycle power with all sensors connected.
• Replace defective sensor.
Too much error
CHECK SENSOR
The value entered in Set Temperature
fi eld is greater than 20 °C (36 °F)
deviation from sensor input. (The 8350
allows a maximum of 20 °C offset.).
• Confi rm calibration values.
• Enter -999 in Set Temperature fi eld.
• Replace defective sensor.
Reset to Factory
Calibration
Value in SET TEMPERATURE fi eld
is -999.
Entering "-999" in this fi eld will remove all user
calibration input and restore the factory values.
Open Collector is always
activated
Hysteresis value too large.
Defective transmitter.
Change the hysteresis value
Replace transmitter
Value must be
400 or less
Value entered in Output PlsRate fi eld is
greater than 400.
Select a maximum pulse rate of 400 pulses per
minute or less.
SETUP READ ERROR
Press Any Key
Memory fault occurred.
• Press any key to reload factory presets.
• Reprogram all setpoints.
• If this message appears again, replace the
8350.