8350-3 Temperature Transmitter

Delta Temperature (Differential Mode)
If two sensors are connected to the transmitter, the DELTA
(Sensor 1 - Sensor 2) can be assigned to output. To enable
differential mode, the selected output "Source" selection must be
set to "DT".

Sensor 1 must be equal to ID 1. If it is not, go to the Calibrate
menu and switch the sensor ID.

In the example below, Sensor 1 is measuring 80º while sensor 2
is measuring 20º. The delta is 60º ( Sensor 1 - Sensor 2 = 60º)

To track the delta temperature using a 4-20 mA output:
Loop1 Source: DT
Loop1 Range: 0-100
Loop1: = 13.60 mA

To set a delta temperature
setpoint using an Open
Collector output:
Output1 Source: DT
Output1 Mode: Low
Output1 Setpoint: 70
Output1 = ON

Temp1: 25.0 ˚C
Temp2: 25.0 ˚C

ENTER

Signet Temperature

Transmitter

View Menu

3.3 Open Collector Output
The Open Collector output can be used as a switch that responds
when the process value moves above or below a setpoint, or it
can be used to generate a pulsing signal with a rate proportional
to the process value.

Low:
Output energizes when
process variable is less
than the setpoint. The
output de-energizes
when the process
variable moves above
the setpoint plus the
hysteresis value.

High:
Output energizes
when process variable
is greater than the
setpoint. The output de-energizes when the process variable
moves below the setpoint plus the hysteresis value.

Hysteresis

Time

Low Setpoint

Process

Relay energized

Relay de-energized

Hysteresis

Time

High Setpoint

Process

10

5

Open Collector Output Rate:

0 to 100 Pulses/min.

endpoint

Pulse rate

0 pulses

100 pulses

Starting point

ENTER

Sensor 1 (80)

Sensor 2 (20)

Proportional

Pulsing

The Open Collector output will generate a 100 mS pulse at the rate defi ned by settings in the
CALIBRATE menu (see page 6)

In the example:
• The output will be 0 pulses/min. at temperatures less than 5º.
• The output will be 50 pulses/min. at 7.5º.
• The output will be 100 pulses/min. at temperatures above 10º.

The starting point, endpoint and maximum pulse rate are select able in the menu.

Display

Description

Temp1: 28.7ºC

Temp2: 19.5ºC

Monitor Temperature 1 and Temperature 2 simultaneously.
This is the permanent view display.

DeltaTemperature:

9.2ºC

Monitor the delta temperature (Channel 1 rate - channel 2 rate = Delta
Temperature). This is a permanent display.

The displays below are temporary. After 10 minutes the display returns to the permanent display.

Loop 1 Output:

12.00 mA

Monitor the 4 to 20 mA output for Loop 1 and 2.

Loop 2 Output:

7.65 mA

Last CAL:

02-10-09

Monitor date for scheduled maintenance or date of last calibration.
(See description in Calibrate Menu.)

• During normal operation, ProcessPro displays the VIEW menu.
• When editing CALIBRATE or OPTIONS menus, ProcessPro returns to the VIEW menu if no activity occurs for

10 minutes.

• To select a VIEW display, press the or keys. The selections will scroll in a continuous loop.
• Changing the display selection does not interrupt system operations.
• No key code is necessary to change display selection.
• Output settings cannot be edited from the VIEW menu.

4. Menu

Functions