8350-3 Temperature Transmitter

Menu items will repeat for Loop 2 and Output 2.

Options Menu

Display

(Factory settings shown)

Description

Contrast:

3 >

Adjust the LCD contrast for best viewing. A setting of 1 is lowest contrast, 5 is highest. Select
lower contrast if the display is in warmer ambient surroundings.

Averaging

Off >

OFF provides the quickest output response to changes in temperature. Longer averaging
period produces more stable display and output response. Select LOW, HIGH or OFF.

Output1 Active

Low

> Active HIGH: This setting is used to turn a device (pump, valve) ON at the setpoint.

Active LOW: This setting is used to turn a device OFF at the setpoint.

Output2 Active

Low >

Loop1 Adjust

4.00 mA

>

Adjust the minimum and maximum current output. Use this setting to match the system output
to any external device. The display value represents the precise current output.
Adjustment limits:
• 3.80 mA < 4.00 mA > 5.00 mA
• 19.00 mA < 20.00 mA > 21.00 mA

Loop1 Adjust

20.00 mA

>

Test Loop 1:

>

Press ▲ or ▼ keys to manually order any output current value from 3.6 mA to 21.00 mA to test
current loop output.

Test Loop 2:

>

Test Output 1:

>

Press ▲ or ▼ keys to manually toggle the state of open collector output.

Test Output 2:

>