Burkert Type 8045 User Manual
Page 70

66
Maintenanceandtroubleshooting
9.5.5.
resolution of problems without message generation and 
device status leD orange
Device	
status	
leD
current	
output	
Ao1
output	Do1	
and/or	Do2	
and/or	Do3
message	
displayed
possible cause
recommended action
orange
4-20 mA Switched
1)
"PULS.	
OVF"
The	value	parametered	
for	the	pulse	output	is	
wrong	(generated	fre-
quency	is	>	250	Hz).
→
Increase	the	value	of	the	
PU	parameter	(see	chap.	
“8.6.7”).
orange
4-20 mA Switched
1)
"NEG.	
FLOW"
The	measured	flow	rate	
is	negative	(although	the	
display	shows	a	positive	
flow	rate).
→
Check	that	the	reverse	fluid	
circulation	has	no	conse-
quences	on	the	process.
→
Else,	mount	the	device	on	
the	pipe	such	as	the	arrow	
on	the	housing	indicates	the	
flow	direction.
orange
4-20 mA Switched
1)
"WARN.	
LOW"
The	measured	flow	rate	
is	below	the	authorized	
low	limit.
This	message	appears	
when	the	flow	rate	
is	monitored	(see	
chap.	8.7.5).
→
Check	the	flow	rate	in	the	
pipe	and	its	consequences	
on	the	process.
→
If	necessary,	clean	the	flow	
sensor	then	calibrate	the	flow	
zero	point.
orange
4-20 mA Switched
1)
"WARN.	
HIG"
The	measured	flow	rate	
is	above	the	authorized	
high	limit.
This	message	appears	
when	the	flow	rate	
is	monitored	(see	
chap.	8.7.5).
→
Check	the	flow	rate	in	the	
pipe	and	its	consequences	
on	the	process.
→
If	necessary,	clean	the	flow	
sensor	then	calibrate	the	flow	
zero	point.
orange
4-20 mA Switched
1)
"DISP. OVF" The real flow rate cannot
be	displayed	(display	is	
saturated).
Except	the	display,	
the	device	operates	
depending	on	the	earl	
flow	rate.
→
Adjust	the	unit	or	the	number	
of	decimals	in	the	UNIT	
parameter	of	the	Parameters	
menu	so	that	the	display	can	
show	higher	values.
orange
4-20 mA Switched
1)
"LIN. LOST" The factory calibration is
lost.
The	device	measures	
wrong	values.
→
Take contact with the retailer.
orange
4-20 mA Switched
1)
"CAL. FAIL"
The	flow	zero	point	cali-
bration	failed.
→
Follow	the	calibration	con-
ditions	described	in	chap.	
8.7.2.
1)
If the output is configured to switch when a warning message is generated. See chap. 8.6.5.
English
Type 8045