Configuring the filter of the measured flow rate, Fig. 47 – Burkert Type 8045 User Manual
Page 53

49
Operatingandfunctions
The daily totalizer is maintained to zero until the digital input switches again.
iNPUt
Di1
REs. tOt.
REtURN
iNV YEs
iNV NO
0......9
→
Choose "INV. NO" to trigger the input on the leading
edge.
→
Choose "INV. NO" to trigger the input on the trailing
edge.
→
Confirm
Fig. 47:
Configuration of the digital input to trigger the reset of the daily totalizer
→
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.
8.6.13. configuring the filter of the measured flow rate
This parameter makes it possible to dampen the fluctuations:
• of the display,
• of the AO1 current output.
Ten filters are available.
When the "fast" filter is active and the flow rate varies for ±30 % (for example when charging the pipe or
stopping the flow), the filter is disabled: the new flow rate is immediately taken into account by the device.
If a too high filter is chosen, the device does not detect the sudden flow rate changes thus the flow rate in
the pipe may strongly defer from the displayed flow rate or the flow rate transmitted to the current output.
FiLtER
FiLtER 0
tOtAL
sLOw
FAst
0......9
→
Choose the slow or fast filter.
→
Confirm
→
Choose the filter.
→
Confirm
FiLtER 9
0......9
Fig. 48:
Diagram of the "FILTER" parameter of the Parameters menu
The following table shows for each filter, the response times (10% to 90%):
English
Type 8045