Configuring the filter of the measured flow rate, Fig. 47 – Burkert Type 8045 User Manual
Page 53

49
Operatingandfunctions
The daily totalizer is maintained to zero until the digital input switches again.
iNPUt
Di1
REs. tOt.
REtURN
iNV YEs
iNV NO
0......9
→
Choose	"INV.	NO"	to	trigger	the	input	on	the	leading	
edge.
→
Choose	"INV.	NO"	to	trigger	the	input	on	the	trailing	
edge.
→
Confirm
Fig. 47:
Configuration of the digital input to trigger the reset of the daily totalizer
→
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.
8.6.13. configuring the filter of the measured flow rate
This parameter makes it possible to dampen the fluctuations:
• of the display,
• of the AO1 current output.
Ten filters are available.
When	the	"fast"	filter	is	active	and	the	flow	rate	varies	for	±30	%	(for	example	when	charging	the	pipe	or	
stopping	the	flow),	the	filter	is	disabled:	the	new	flow	rate	is	immediately	taken	into	account	by	the	device.
If	a	too	high	filter	is	chosen,	the	device	does	not	detect	the	sudden	flow	rate	changes	thus	the	flow	rate	in	
the	pipe	may	strongly	defer	from	the	displayed	flow	rate	or	the	flow	rate	transmitted	to	the	current	output.
FiLtER
FiLtER 0
tOtAL
sLOw
FAst
0......9
→
Choose the slow or fast filter.
→
Confirm
→
Choose the filter.
→
Confirm
FiLtER 9
0......9
Fig. 48:
Diagram of the "FILTER" parameter of the Parameters menu
The following table shows for each filter, the response times (10% to 90%):