62
Maintenanceandtroubleshooting
9.5.
If you encounter problems
9.5.1.
resolution of problems when the device status leD is off
Device	
status	
leD
current	
output	
Ao1
output	Do1	
and/or	Do2	
and/or	Do3
message	
displayed
possible cause
recommended action
OFF
0 mA
low level
"PWRFAIL"
The	supply	voltage	is	too	
low.
The	device	does	not	
function.
→
Check	that	the	supply	
voltage	is	between	18	and	
36	V	DC.
→
If	the	problem	occurs	again,	
take	contact	with	the	retailer.
OFF
0 mA
not switched
-
The	device	is	not	
energized.
→
Check the wiring.
→
Check	the	fuse	of	the	
installation	and	replace	it	if	
necessary.
→
Check	that	the	installation	is	
not	shut-down.
→
Check	that	the	power	source	
is	working	properly.
9.5.2.
resolution of problems without message generation but 
device status leD on
Device	
status	leD
current	
output	
Ao1
output	Do1	
and/or	Do2	
and/or	Do3
problem
recommended action
any colour
4-20 mA
depending	on	
the	thresholds	
or	switched	
1)
Access	to	the	Param-
eters	and	Test	menus	is	
impossible.
→
Check	the	position	of	the	"ENTER	key	
lock/unlock"	switch.	See	chap.	“7.3.3”.
any colour
0 mA
depending	on	
the	thresholds	
or	switched	
1)
The	current	output	
transmits	0	mA.
→
Check the wiring of the current output.
→
Check	the	fuse	of	the	installation	and	
replace	it	if	necessary.
→
Check	the	position	of	the	sink/source	
switch.	See	chap.	“7.3.4”.
→
If	the	problem	occurs	again,	take	contact	
with	the	retailer.
The	current	output	
transmits	a	value	
between	0	and	4	mA.
→
Switch	the	device	power	supply	off	then	
on.
→
If	the	problem	occurs	again,	take	contact	
with	the	retailer.
English