Burkert Type 8045 User Manual
Page 69

65
Maintenanceandtroubleshooting
9.5.4.
resolution of problems without message generation and 
device status leD red
Device	
status	
leD
current	
output	
Ao1
output	Do1	
and/or	Do2	
and/or	Do3
message	
displayed
possible cause
recommended action
red
22 mA
depending	on	
thresholds
"ERROR3"
The	user	parameters	and	
the	factory	calibration	are	
lost.
The	device	measures	
wrong	values.
→
Start the device again.
→
If	the	problem	occurs	again,	
take	contact	with	the	retailer.
→
If	the	"LIN.LOST"	message	is	
also	generated,	take	contact	
with	the	retailer.
red
22 mA
depending	on	
thresholds
"ERROR4"
The	totalizer	values	are	
lost.
The	values	saved	upon	
the	next	to	last	power	
down	are	retrieved.
→
Start the device again.
→
If	the	problem	occurs	again,	
take	contact	with	the	retailer.
red
22 mA
depending	on	
thresholds
"ERROR5"
Both	"ERROR3"	and	
"ERROR4".
→
Take contact with the retailer.
red
22 mA
depending	on	
thresholds
"ERROR6"
Totalizers definitely lost.
Both totalizers are reset.
→
Start the device again.
→
If	the	problem	occurs	again,	
take	contact	with	the	retailer.
red
22 mA
depending	on	
thresholds
"ERROR7"
Both	"ERROR3"	and	
"ERROR6".
→
Take contact with the retailer.
red
22 mA
depending	on	
thresholds
"MEAS.	
OVF"
The	flow	rate	in	the	pipe	
is	>	12	m/s.
→
Check	the	flow	rate	in	the	
pipe.
→
If	necessary,	adjust	the	flow	
rate.
→
If	the	problem	occurs	again,	
take	contact	with	the	retailer.
English
Type 8045