beautypg.com

And “fig. 13”) – Burkert Type 3004 User Manual

Page 14

background image

14

Installation

H

A

C

B

C

E

F

D

Fig. 13: Power supply circuit board for actuators with 300 Nm

No. Designations

No.

Designations

A

Screw for earthing

E

LED 2: Error message

B

Connections for control
and power supply

F

LED 3: Power on

C

Fuse

H

Connection 24 V DC

D

LED 1: Microprocessor OK

The rotary actuator can be connected and operated in two dif-
ferent modes:

1.

Three points mode

2.

Open / Closed mode

N

-

Ph

+

1

2

3

T/E

N

-

Ph

+

3

2

1

T/E

Fig. 14: Three points mode

Fig. 15: Open/Closed mode (Consider

the emergency power model in
the operating instructions)

If voltage is applied simultaneously to terminals 2 and 3,
terminal 2 is the leading one and the actuator moves to the
OPEN position.

Procedure:

Loosen left cable gland (pos. 15, “Fig. 1” and “Fig. 2”) land feed
through the cable to be connected.

Connect cable according to the required control type (“Fig. 14” and
“Fig. 15”) to the terminal strip Pos. B of the power supply circuit
board (“Fig. 12” and “Fig. 13”).

english

Type 3004