Burkert Type 8650 User Manual
Page 91
91
2.5.4.
Parameters that can be displayed or modified by channels
Name
Value
Unit
Status
#.#.Channel.0
Channel enable
enable
-
Initial value
Behavior at CPU/Master-STOP
switching alternative value
Alternative value
0
#.#.#.Pilot.valve
Switching cycle counter reset
inactive
-
Initial value
ID number of the pilot valve
0
Initial value
Current number of the switching cycles
74766
-
#.#.#.Actuator
Enable switching cycle counter diagnosis
enable
-
Initial value
Switching cycle counter warning limit
0
Switching cycle counter reset
inactive
Date of the last switching cycle counter reset
-
Current number of switching cycles
74766
-
#.#.#.Diagnosis
Group diagnosis
barred
-
-
Broken wire
Short circuit
2.5.5.
Functions of the channel parameter (general)
• Enable.channel.(read./.write).
Defines whether or not the channel is enabled for use.
• Behavior.at.CPU/Master.STOP.(read./.write).
Defines which value the channel assumes when the master is set to STOP.
• Alternative.values.(read./.write).
Defines the alternative value for the case „Switch alternative value at master STOP“.
2.5.6.
Functions of the parameter actuator (that are connected to
the pilot valve (of this channel)
• Switching.cycle.counter.reset.
Initiates a reset of the actuator switching cycle counter.
• ID.number.of.the.pilot.valve.(read./.write)
.
You can enter the ID number of the pilot valve used here. This makes it quickly available if replacement or pre-
ventive maintenance are forthcoming.
• Current.number.of.switching.cycles.(read.only)
.
Indicates how many switching cycles the pilot valve has performed since the last counter reset.
Type 8650
english
Commissioning