beautypg.com

Technical data, General technical data, Technical.data – Burkert Type 8650 User Manual

Page 15: . general.technical.data

background image

15

2.

TECHNICAL DATA

2.1.

General Technical Data

Medium

Clean, dry air (oiled or unoiled),
neutral gases (particle size max. 5 μm)

Max. power consumption

see table below “

Power consumption of the active

modules”.

Ambient temperature during
operation

0 °C to +55 °C

Storage temperature

-20 °C to +60 °C

Relative humidity

5 to 95 %, non-condensing

Acceleration during operation

5 m/s

2

Rated operating mode

100 % CDF ( continuous operation)

Operating voltage

24 V DC in EEx-e
(Details: see Siemens Power Supply Module)

Degree of protection

IP30

Protection class

3 (VDE0580)

Housing materials

Pneumatic modules and valves: PA (polyamide

electronic modules: PBT (polybutylene terephthalate)

Seal materials

Pneumatic modules and valves: NBR

electronic modules: PC (polycarbonate)

Approvals

A prerequisite for the authorized use of the total AirLINE-Ex system is the
installation in a suitable certified housing:

- Ex-e- or Ex-d-housing for Zone 1 respectively
- Ex-d-housing for Zone 21

FA prerequisite for FM-Ex in Zone 21 or Class II, III Div. 1,2 with the sub-
stance classes E, F & G is the operation in a suitable Ex-D housing.

• Electronic modules

ATEX: ATEX II 2 G Ex ib IIC T4 (Zone 1 / 21)

IEC-Ex: IECEx KEM 07.0032

FM-Ex: Class II, III, Div. 1, 2, GP E, F, G

IS Class I, Div. 1 GP A, B, C, D T4
Class I, Div. 2 GP A, B, C, D T4
Class I, Zone 1, AEx ib IIC T4

• Terminal modules

ATEX: ATEX II 2 G Ex e [ia/ib] IIC T4 (Zone 1 / 21)

IEC-Ex: IECEx KEM 07.0033

FM-Ex: Class II, III, Div. 1, 2, GP E, F, G

IS Class I, Div. 1, GP A, B, C, D T4

Class I, Div 2, GP A, B, C, D T4

Class I, Zone 1 e [ia/ib] IIC T4

The AirLINE Ex satisfies the requirements of the EMC Act.

Interference resistance EN 50082-2
Emitted interference EN 50081-2

Type 8650

english

System Description