2.
TECHNICAL DATA
2.1.
General Technical Data
Medium
Clean, dry air (oiled or unoiled),
neutral gases (particle size max. 5 μm)
Max. power consumption
see table below “
Power consumption of the active
modules”.
Ambient temperature during
operation
0 °C to +55 °C
Storage temperature
-20 °C to +60 °C
Relative humidity
5 to 95 %, non-condensing
Acceleration during operation
5 m/s
2
Rated operating mode
100 % CDF ( continuous operation)
Operating voltage
24 V DC in EEx-e
(Details: see Siemens Power Supply Module)
Degree of protection
IP30
Protection class
3 (VDE0580)
Housing materials
Pneumatic modules and valves: PA (polyamide
electronic modules: PBT (polybutylene terephthalate)
Seal materials
Pneumatic modules and valves: NBR
electronic modules: PC (polycarbonate)
Approvals
A prerequisite for the authorized use of the total AirLINE-Ex system is the
installation in a suitable certified housing:
- Ex-e- or Ex-d-housing for Zone 1 respectively
- Ex-d-housing for Zone 21
FA prerequisite for FM-Ex in Zone 21 or Class II, III Div. 1,2 with the sub-
stance classes E, F & G is the operation in a suitable Ex-D housing.
• Electronic modules
ATEX: ATEX II 2 G Ex ib IIC T4 (Zone 1 / 21)
IEC-Ex: IECEx KEM 07.0032
FM-Ex: Class II, III, Div. 1, 2, GP E, F, G
IS Class I, Div. 1 GP A, B, C, D T4
Class I, Div. 2 GP A, B, C, D T4
Class I, Zone 1, AEx ib IIC T4
• Terminal modules
ATEX: ATEX II 2 G Ex e [ia/ib] IIC T4 (Zone 1 / 21)
IEC-Ex: IECEx KEM 07.0033
FM-Ex: Class II, III, Div. 1, 2, GP E, F, G
IS Class I, Div. 1, GP A, B, C, D T4
Class I, Div 2, GP A, B, C, D T4
Class I, Zone 1 e [ia/ib] IIC T4
The AirLINE Ex satisfies the requirements of the EMC Act.
Interference resistance EN 50082-2
Emitted interference EN 50081-2
Type 8650
english
System Description