. repair, Repair – Burkert Type 8650 User Manual
Page 106
106
Fault
Possible.cause
Remedy
SF LED lights up.
Wrong configuration.
→
Use the corresponding module from the
hardware catalogue.
Valve diagnosis trips (short circuit,
open outlet port).
→
Check the proper installation of the valve.
→
Replace defective valves.
→
Deactivate the diagnosis for valve posi-
tions not in use.
Module does not start due to
internal current limit (short circuits at
the outlet ports).
→
Remedy the short circuits (defective
valves at the outlet ports)
→
Carry out a voltage reset of the module /
system.
If an ET200iSP station has started once with Profibus address X, the address can be changed as follows:
→
Switch off the station.
→
Set the address 0 (all DIP switches in position OFF).
→
Switch on the station and wait approx. 10 seconds.
→
Switch off the station and wait approx. 10 seconds again.
→
Set the desired new address Y.
→
Switch on the station.
The new address is stored.
3.4.
Repair
If a repair is necessary, send the module to your local Bürkert subsidiary or contact our After-Sales Service.
Address and telephone number can be found in the chapter „General Information / Scope of Supply“.
Type 8650
english
Maintenance and Repair