beautypg.com

Burkert Type 8686 User Manual

Page 41

background image

41

Malfunctions

13

malfuncTiOns

malfunction

cause and remedial action

End position is
not detected

No or inadequate supply voltage

Check the electrical connection and supply
voltage

Wrong size of switch spindles from the adapter
set

Replace switch spindles

Wrong spindle lead-through selected for
spindle installation

Push the switch spindle through the
matching spindle lead-through

Wrong actuator size selected with the DIP
switches

Select the matching actuator size

Cap of the switch spindle moved by force
during assembly

Remove the feedback head / control head

Pull the cap towards the end of the switch
spindle until you can see one groove

Install the feedback head / control head

Perform a reference movement for spindle
adjustment

malfunction

cause and remedial action

Faulty detection
of end position

Wrong actuator size selected with the DIP
switches

Select the matching actuator size

More than one actuator size selected with the
DIP switches

Select the matching actuator size

Feedback head / control head not mounted in
the correct position

Mount the feedback head / control head in
the correct position (see “Fig. 9”)

Incorrect
display of
actuator status
LED

Color selection switch not correctly selected

Select the color assignment correctly (both
up or both down, see section “10.3.1 Basic
settings” “Fig. 29”)

Actuator does
not switch

No or inadequate supply voltage

Check the electrical connection and supply
voltage

Pressure supply too low

Check the control pressure

Faulty hose system

Check the pneumatic connections

English

Type 8685 / 8686

This manual is related to the following products: