Maintenance

12.2 service at the air intake filter

Danger!

risk of injury from high pressure in the equipment/device.

▶ Before working on equipment or device, switch off the pressure

and deaerate/drain lines.

To protect the internal pilot valves and the actuator, the control air is
filtered.
The direction of flow of the air intake filter in installed state is from
the inside to the outside through the filter material.

Air intake filter

Quick connector

O-ring

Fig. 34: Service at the air intake filter

procedure:

Unlock the quick connector by pressing the holding element and
pulling out the air intake filter (if necessary, use a suitable tool in
between the recesses in the head of the filter).

Clean the filter or, if necessary, replace the filter.

Check inner O-ring and, if required, clean.

Insert the air intake filter all the way into the quick connector.

Danger!

risk of injury due to improper installation.

▶ Ensure that the air intake filter is installed correctly.

Check that the air intake filter is secure.