beautypg.com

Burkert Type 8686 User Manual

Page 22

background image

22

Electricalinstallation

GND

24V

Top1

Bot1

Top2

Bot2

Fig. 15: Designation on PCB Type 8685

designation
on pcB

assignment

1)

24 V

Supply voltage +

24 V DC ±10%

GND

Supply voltage -

GND

Top 1

Top end position -
Top actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

Bot 1

Bottom end position -
Bot actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

Top 2

Top end position -
Top actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

Bot 2

Bottom end position -
Bot actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

Tab. 4: Connection for cable gland Type 8685

1)

Actuator assignment see “Fig. 16”.

Pilot air port

2 (P2)

Pilot air port
4 (P4)

Pilot air port
3 (P3)

Pilot air port

1 (P1)

actuator 1

(left)

actuator 2
(right)

Fig. 16: Pneumatic connection

Connect the wires (see pin assignment in “Tab. 4”).

note!

damage or malfunction due to ingress of dirt and moisture.

▶ To ensure degree of protection IP65 / IP67, tighten the union

nut of the cable gland according to the cable size you are using

(approx. 1.5 Nm).

Tighten the union nut of the cable gland on the body (approx. 1.5
Nm).

English

Type 8685 / 8686

This manual is related to the following products: