22
Electricalinstallation
GND
24V
Top1
Bot1
Top2
Bot2
Fig. 15: Designation on PCB Type 8685
designation
on pcB
assignment
1)
24 V
Supply voltage +
24 V DC ±10%
GND
Supply voltage -
GND
Top 1
Top end position -
Top actuator 1
24 V / 0 V (max. 0.1 A)
GND (7)
Bot 1
Bottom end position -
Bot actuator 1
24 V / 0 V (max. 0.1 A)
GND (7)
Top 2
Top end position -
Top actuator 2
24 V / 0 V (max. 0.1 A)
GND (7)
Bot 2
Bottom end position -
Bot actuator 2
24 V / 0 V (max. 0.1 A)
GND (7)
Tab. 4: Connection for cable gland Type 8685
1)
Actuator assignment see “Fig. 16”.
Pilot air port
2 (P2)
Pilot air port
4 (P4)
Pilot air port
3 (P3)
Pilot air port
1 (P1)
actuator 1
(left)
actuator 2
(right)
Fig. 16: Pneumatic connection
→
Connect the wires (see pin assignment in “Tab. 4”).
note!
damage or malfunction due to ingress of dirt and moisture.
▶ To ensure degree of protection IP65 / IP67, tighten the union
nut of the cable gland according to the cable size you are using
(approx. 1.5 Nm).
→
Tighten the union nut of the cable gland on the body (approx. 1.5
Nm).
English