20

Pneumaticinstallation

8.2

pneumatic installation of
feedback head Type 8685

The feedback head does not require a pilot air supply.

A description of the pneumatic installation of the actuator is
included in the valve operating instructions.

8.3

pneumatic installation of control
head Type 8686

Danger!

risk of injury from high pressure in the equipment/device.

▶ Before working on equipment or device, switch off the pressure

and deaerate/drain lines.

procedure:

Connect the control medium to the pilot air port (1)
(6 – 7 bar; instrument air, free of oil, water and dust).

Mount the exhaust air line or a silencer on the exhaust air port (3)
(see “Fig. 13: Pneumatic connection Type 8686”).

Important information for the problem-free functioning of
the device:

▶ The installation must not cause back pressure to build up.

▶ To make the connection, select a hose with sufficient cross

section.

▶ The exhaust air line must be designed in such a way that

no water or other liquid can get into the device through the

exhaust air connection (3).

Pilot air port
Label: 1

Exhaust air port
Label: 3

Fig. 13: Pneumatic connection Type 8686

Caution

(exhaust air concept): In compliance with degree

of protection IP65 / IP67, an exhaust air line must be
installed in the dry area.
always maintain an applied control pressure of at least
0.5 – 1 bar above the pressure which is required to move the
actuator to its end position.