beautypg.com

Burkert Type 8686 User Manual

Page 24

background image

24

Electricalinstallation

9.2.2 electrical installation of control head

Type 8686

device connection for circular plug-in connector type 8686

Connect the circular plug-in connector of the control head as
described in “Tab. 5”.

6

1

7

5

4

3

2

8

Fig. 17: Assignment of circular plug (M12 x 1, 8-pole)

Use only straight connecting socket.

Pilot air port

2 (P2)

Pilot air port
4 (P4)

Pilot air port
3 (P3)

Pilot air port

1 (P1)

actuator 1

(left)

actuator 2
(right)

Fig. 18: Pneumatic connection

When the supply voltage is applied, the control head is operating.

Before the device can be used, the basic settings (see section
“10.3.1 Basic settings”) must still be made on the control head.

pin

wire
color

2)

assignment

3)

external circuit

1

white

Bottom end position -
Bot actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

1

2

brown

Top end position -
Top actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

2

3

green

Bottom end position -
Bot actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

3

4

yellow

Top end position -
Top actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

4

5

gray

Valve control Y2
Actuator 2 activated

high active, to activate
connect with 24 V

5

6

pink

Valve control Y1
Actuator 1 activated

high active, to activate
connect with 24 V

6

7

blue

Supply voltage –

GND

7

8

8

red

Supply voltage +

24 V DC ±10%

Tab. 5: Connection for circular plug-in connector Type 8686

2)

The indicated colors refer to the connecting cable available as an
accessory (919061).

3)

Actuator assignment see “Fig. 18”.