Burkert Type 8686 User Manual
Page 29
29
Electricalinstallation
Bit configuration
data bit
inputs
function
assignment
5)
D0
Top end position -
Top actuator 1
0 Top not reached
1 Top reached
D1
Bottom end position -
Bot actuator 1
0 Bot not reached
1 Bot reached
D2
Top end position -
Top actuator 2
0 Top not reached
1 Top reached
D3
Bottom end position -
Bot actuator 2
0 Bot not reached
1 Bot reached
data bit
Outputs
function
assignment
5)
D0
-
not used
D1
-
not used
D2
-
not used
D3
-
not used
Tab. 9:
Bit configuration of AS-Interface for feedback head Type 8685
Parameter bits have no function.
5)
Actuator assignment see “Fig. 23”.
programming data for control head type 8686:
I/O configuration
7 hex
ID code
A hex (see below for bit configuration)
Extended ID code 1
7 hex
Extended ID code 2
E hex
Profile
S-7.A.E
Tab. 10: Programming data for control head Type 8686
Pilot air port
2 (P2)
Pilot air port
4 (P4)
Pilot air port
3 (P3)
Pilot air port
1 (P1)
actuator 1
(left)
actuator 2
(right)
Fig. 23: Pneumatic connection
English
Type 8685 / 8686