Electricalinstallation

Bit configuration

data bit
inputs

function

assignment

6)

D0

Top end position -
Top actuator 1

0 Top not reached
1 Top reached

D1

Bottom end position -
Bot actuator 1

0 Bot not reached
1 Bot reached

D2

Top end position -
Top actuator 2

0 Top not reached
1 Top reached

D3

Bottom end position -
Bot actuator 2

0 Bot not reached
1 Bot reached

data bit
Outputs

function

assignment

6)

D0

Pilot valve Y1

0 Pilot valve OFF
1 Pilot valve ON

D1

Pilot valve Y2

0 Pilot valve OFF
1 Pilot valve ON

D2

-

not used

D3

-

not used

Tab. 11: Bit configuration of AS-Interface for control head Type 8686

Parameter bits have no function.

6)

Actuator assignment see “Fig. 24”.

9.3.5 leD status display for as-interface

status led 1
(green)

status led 2
(red)

off

off

POWER OFF

off

on

No data traffic (expired Watch
Dog at slave address does not
equal 0)

on

off

OK

flashing

on

Slave address equals 0

Tab. 12: LED status display for AS-Interface

Pilot air port

2 (P2)

Pilot air port
4 (P4)

Pilot air port
3 (P3)

Pilot air port

1 (P1)

actuator 1

(left)

actuator 2
(right)

Fig. 24: Pneumatic connection

English

Type 8685 / 8686