3 smart display modes, continued – Alpha Technologies XM2, XM2-HV, XM2-HP User Manual
Page 63

4.3
Smart Display Modes, continued
4.3.4 Menu Structure/Navigation
(from Operation Normal screen)
COMMS INFO
TEST: 10 MIN
37.3 V
+
OPERATION NORMAL
(Auto-Scroll )
To Single-step
Back to Auto-Scroll
Back to
Auto-Scroll
Only visible in single-step mode
To Self-test
To COMMS INFO
To Operation Normal
COMMS INFO
(Single-step)
To Single-step
(Single-step)
(Auto-Scroll )
OPERATION NORMAL
Back Auto-Scroll
BATT VOLTAGE
To Single-step
Back to Auto-Scroll
SETUP MENU
(Auto-scroll)
220GOLD
220HPL-FT
220GXL
210GXL
195GXL
195GOLD
180GXL
165GXL
115HPL-FT
85GXL
70HPL-FT
Float V/C = 2.27 V
SETUP MENU
CODE VER = 7.01.0
DEVICE ADDRESS= 1
ALPHACELL = OTHER
FLOAT V/C=2.27
ACCEPT V/C=2.40
TEMP COMP=5mV
BATT CAPACITY=100Ah
STANDBY TIME=65M
STANDBY EVENTS=12
TOTAL RUN TIME = 365D
SELF TEST = OFF
TEST INHIBIT
TEST INTERVAL
TEST DURATION = 10M
TEST COUNTDOWN
FREQ RANGE = 3.0Hz
PIM OPTION = YES
RESET OUT 1
RESET OUT 2
OVERCURRENT 1 = 15.0A
OVERCURRENT 2 = 15.0A
RETRY DELAY = 60s
RETRY LIMIT = 20
OVER CURR TOL = 3000
N+1 VALID = NO
SET DEFAULTS = NO
SELECT LANGUAGE
OPER MODE = LINE
INPUT VOLTAGE 120V
INPUT FREQUENCY 60Hz
OUTPUT VOLTAGE 89V
OUTPUT 1 CURRENT 12.2A
OUTPUT 2 CURRENT 12.0A
OUTPUT WATTS (W)
OUTPUT VA 1060
PERCENT LOAD 80%
CHARGER MODE = FLOAT
BATT VOLTAGE 40.5V
BATTERY TEMP 37°C
CHARGER CURRENT 8.2A
12 EVENTS 65 MIN
(Single-step)
CODE VER = 7.01.0
DEVICE ADDRESS= 1
ALPHACELL = OTHER
FLOAT V/C=2.27
ACCEPT V/C=2.40
TEMP COMP=5mV
BATT CAPACITY=100Ah
STANDBY TIME=65M
STANDBY EVENTS=12
TOTAL RUN TIME = 365D
SELF TEST = OFF
TEST INTERVAL
TEST INHIBIT
TEST DURATION = 10M
TEST COUNTDOWN
FREQ. RANGE = 3.0Hz
TAP SWITCH
PIM OPTION = YES
RESET OUT 1
RESET OUT 2
OVERCURRENT 1 = 15.0A
OVERCURRENT 2 = 15.0A
RETRY DELAY = 60s
RETRY LIMIT = 20
OVER CURR TOL = 3000
N+1 VALID = NO
SET DEFAULTS = NO
SELECT LANGUAGE
Appears only in Auto-scroll mode
To Program Mode
To Accept New Data
To Accept
New Data
To Abort
Edit using
Back to Single-st
ep Setup Menu
LANGUAGE =
ENGLISH
SPANISH
FRENCH
PORTUGUESE
GERMAN
Back to Single-st
ep Setup Menu
OPER MODE = LINE
INPUT VOLTAGE 120V
OUTPUT VOLTAGE 89V
OUTPUT 1 CURRENT 12.2A
OUTPUT 2 CURRENT 12.0A
CHARGER MODE = FLOAT
BATT VOLTAGE 40.5V
BATTERY TEMP 37°C
CHARGER CURRENT 8.2A
12 EVENTS 65 MIN
+
Back to Operation Normal
Self-test OFF
CM = 00:90:EA:00:30:54
CM192.168.1.151
CMRx PWR -6.8dBMv
CMTx PWR 41.0dBMv
DN FREQ = 300.000 MHz
UP FREQ = 15.000 MHz
SW 4.5.9.0_00.77CO-N
BATT A1=13.1 A2=14.0
BATT A3=13.5 B1=13.1
BATT B2=14.0 A2=13.5
CM = 00:90:EA:00:30:54
CM192.168.1.151
CMRx PWR -6.8dBMv
CMTx PWR 41.0dBMv
DN FREQ = 300.000 MHz
UP FREQ = 15.000 MHz
SW 4.5.9.0_00.77CO-N
BATT A1=13.1 A2=14.0
BATT A3=13.5 B1=13.1
BATT B2=14.0 A2=13.5
Displayed when
AlphaCell = Other selected.
When an AlphaCell battery is
selected, the values for Float,
Accept, Temp Comp and
Battery Capacity are
automatically selected and not
shown in the Smart Diaplay.
Once the battery data has
been updated, the operator
will be prompted to select the
number of battery strings used
in the system.
Displayed only when
optional PIM is installed.
Displayed only
when optional
PIM is installed.
Displayed when
AlphaCell = Other
selected.
LEGEND
Description
Control panel
Key
Smart Display
Symbol
UP
DOWN
ENTER
ESCAPE
63
017-805-B0-010 Rev. K2