Alpha Technologies XM2, XM2-HV, XM2-HP User Manual
Page 42

3.1
Power Distribution Board (PDB) Setup, continued
The jumpers (JP-1 and JP-2) and switches (SW-1, SW-2) are located on the Power
Distribution Board (PDB) as shown below.
Fig. 3-1, Locations of JP1, JP2 and SW1, SW2 on the Power Distribution Board (PDB)
JP 1
When configured for 120Vac Operation, the pins on
both JP1 and JP2 will be OPEN.
Two-pin jumper
JP 2
SW 1(Output)
SW 2 (Input)
Some models of the PDB’s JP1 and JP2 are two-pin jumpers, while other models have three-
pin jumpers. The voltages are configured as shown below.
120
240
When configured for 240Vac Operation, the pins on
both JP1 and JP2 will be SHORTED.
When configured for 120Vac Operation, on both JP1
and JP2 the pin marked “120” and the center pin will
be shorted as shown.
120
240 120
240
JP1
JP2
120
240
JP1
JP2
When configured for 120Vac Operation, on both JP1
and JP2 the pin marked “240” and the center pin will
be shorted as shown.
JP1
JP2
JP1
JP2
Three-pin jumper
42
017-805-B0-010 Rev. K2
- AlphaCell GelCell Series (32 pages)
- FXM 650, 1100, 2000 UPS (96 pages)
- Cordex 48-1.2kW (68 pages)
- Radium MiniBay (57 pages)
- Fiber Backhaul Enclosure (FBE) (19 pages)
- FBE2322 Enclosure System (38 pages)
- FlexNet PMR, GMR Series (49 pages)
- Te25xh (38 pages)
- FlexNet MPS48-12M - Technical Manual (33 pages)
- FlexNet MPS48-12M - Quick Start Guide (2 pages)
- FlexNet ELPM 300-48D (25 pages)
- FlexNet FMPS (40 pages)
- FlexPoint AX Series (34 pages)
- FlexPoint FPR1207-F - Technical Manual (18 pages)
- FlexPoint FPR1207-F - Quick Start Guide (2 pages)
- AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual (79 pages)
- AlphaGen CE-3x2 5K-T 48Vdc (95 pages)
- AlphaGen PN-6x-T 7.5kW 48Vdc (95 pages)
- AlphaGen 3.5_5.0kW Kohler COM5 (80 pages)
- Security Bar Field For UPE-3, UPE-6, UPE-M3, UPE-M6, PN Series and CE Series (2 pages)
- AMPS80 HP (116 pages)
- 255A Bypass Switch (24 pages)
- AMP24 HP (108 pages)
- FXM350_Micro350 UPS (112 pages)
- CFR 600, CFR 600XT, CFR 1000 (70 pages)
- BPS Series Bypass Switch (36 pages)
- CFR Intelligent Interface Device (54 pages)
- CFR Redundant Control Unit (23 pages)
- CFR 5000, CFR 5000RM (88 pages)
- CFR 3000, CFR 3000RM (86 pages)
- CFR 1500, CFR 1500RM (83 pages)
- CFR 1500, CFR 2000, CFR 2500, CFR 3000 (76 pages)
- Continuity: 1000_2000_3000 (48 pages)
- Continuity Battery Pack (20 pages)
- Continuity: 6K_10K (52 pages)
- Micro, Micro XL, Micro XL3 UPS (99 pages)
- Micro Secure UPS (80 pages)
- Te17 (32 pages)
- Te45 (68 pages)
- Te41, 48V (76 pages)
- Te41, 24V (72 pages)
- Te43 (60 pages)
- AlphaGuard AG-CMT Installation (2 pages)
- AlphaGuard AG-CMT-3SC_4SC-P (2 pages)
- Digital Midtron DM-3200 AT (2 pages)