79

Doc. #: 026-069-B0 Rev F

7.4 Replacing the T2S Inverter Control Card

CAUTION!

Perform this procedure with the system in bypass mode and/or during a scheduled

maintenance window.

CAUTION!

Ignore error/alarm conditions displayed during initialization. Do not remove any system

components during the initialization sequence. Interruptions to the initialization sequence

can result in software corruption and reduced functionality.

Step 1: Removal

To release the T2S from the shelf, insert a small flat screwdriver in the

square hole under the USB port and lift up the lock pin. Then pull out the

module.

Step 2: Replacement and Initialization

Insert the new T2S into the system. Once inserted, it will take about 10

minutes (or longer with fully loaded systems) for the T2S to initialize with

the inverter modules.

When the T2S is initially

inserted, all LEDS are off

for a few seconds.

Initialization is in progress:

Top 2 LEDs: solid green

Bottom LED: off

DO NOT INTERRUPT

Initialization complete:

Top 2 LEDs : solid green

Bottom LED: flashing green

Figure 56 —

T2S LED sequence during initialization