12 set output – Alpha Technologies AMPS80 HP User Manual
Page 69

67
Doc. #: 026-069-B0 Rev F
6.3.12 Set Output
This submenu of Inverters will enable the supervisor to modify the following parameters:
Figure 48 —
Set Output window
For inverters,changes
apply on a page by
page basis; select
Submit
.
Select
Cancel
to
discard all changes
made (including
invalid settings).
An invalid setting (for any
configurable parameter)
will be indicated with a
red exclamation mark.
Hovering the mouse on
the exclamation mark re-
veals the error message.
!
CAUTION!
The value entered in the Nominal Output Voltage field can change the actual AC output
voltage of the inverters. Setting this value to anything other than 120 V will render the UL/
CSA approval invalid.
Number of Modules
Total number of inverter modules installed for that phase. Setting this number to
something different from the actual number of installed modules results in the
alarm condition
Inverter Comms Lost
.
Redundancy
Defines the number of inverter modules that will provide redundant power for that
phase (used to provide system warnings).
Phase shift
Assigns a phase shift (in degrees) to the AC output group.
Nominal Output Voltage
Enter
120
for all phases.
Ensure that the
Phase Shift
is set correctly before mapping inverters in the new groups and turning them on.