Maintenance, 1 preventive maintenance, 2 recommended maintenance schedule – Alpha Technologies AMPS80 HP User Manual
Page 79: 3 tools, spare parts and equipment, Table i — tools
![background image](/manuals/317354/79/background.png)
77
Doc. #: 026-069-B0 Rev F
WARNING!
WARNING: HIGH VOLTAGE AND SHOCK HAZARD Use extreme care when working in-
side the enclosure/shelf while the system is energized. Do not make contact with live com-
ponents or parts. Static electricity may damage circuit boards, including RAM chips. Always
wear a grounded wrist strap when handling or installing circuit boards. Ensure redundant
modules or batteries are used to eliminate the threat of service interruptions while perform-
ing maintenance on the system’s alarms and control settings.
7. Maintenance
7.1 Preventive Maintenance
This equipment requires regular maintenance. The maintenance must be done by qualified service personnel
only. Contact Alpha Technologies at 1-888-462-7487 for any assistance with maintenance.
7.2 Recommended maintenance schedule
Task:
Interval
Clean ventilation openings
1-6 month
Inspect all cable connections, re-torque if necessary
1 year
Verify alarm/control settings
1 year
Verify alarm relay operation
1 year
Verify circuit breaker operation
1 year
7.3 Tools, Spare Parts and Equipment
Table I — Tools
Required
Service /Maintenance
Commissioning
Torque wrench
X
X
#2 Philips screw driver
X
X
#2 flat head screw driver (3/16") width head
X
#1 flat head screw driver (1/8") width head
X
Small flat head screw driver (1/16") width head
X
X
9/16" hex driver
X
3/8" hex driver
X
7/16" combo wrench
X
7/16" flat gear ratchet
X
9/16" combo wrench
X
9/16" flat gear ratchet
X
11/16" combo wrench
X
11/16" flat gear ratchet
X
6" ratchet extension
X
3" ratchet extension
X