System operation, 1 inverter module indicators, 1 status leds – Alpha Technologies AMPS80 HP User Manual
Page 57

55
Doc. #: 026-069-B0 Rev F
6. System Operation
6.1 Inverter Module Indicators
Output power
indicator LEDs
Status LEDs
Figure 35 —
Fig. 4.1 Inverter module status, power LEDs
6.1.1 Status LEDs
Inverter Status LED
Description
Remedial action
OFF
No input power or forced stop
Check AC input
Permanent green
AC Intput OK, normal operation
None required
Flashing green
Inverter OK but conditions are not
within normal parameters
Check upstream and surrounding equipment
Flashing green/orange alternating Recovery mode after boost
(10 In short circuit condition)
Wait for a while
Permanent orange
Starting-up mode
Wait
Flashing orange
Modules cannot start
Insert CXC
Flashing red
Recoverable fault
Wait or attempt to clear fault condition by
removing and reinserting the module
Permanent red
Non recoverable fault
• Attempt to clear fault condition by
removing and reinserting the module
• Download CXC inverter alarm logs
• Record the alarm(s)
• Send module back for repair
AC input
AC output
DC input
- AlphaCell GelCell Series (32 pages)
- FXM 650, 1100, 2000 UPS (96 pages)
- Cordex 48-1.2kW (68 pages)
- Radium MiniBay (57 pages)
- Fiber Backhaul Enclosure (FBE) (19 pages)
- FBE2322 Enclosure System (38 pages)
- FlexNet PMR, GMR Series (49 pages)
- Te25xh (38 pages)
- FlexNet MPS48-12M - Technical Manual (33 pages)
- FlexNet MPS48-12M - Quick Start Guide (2 pages)
- FlexNet ELPM 300-48D (25 pages)
- FlexNet FMPS (40 pages)
- FlexPoint AX Series (34 pages)
- FlexPoint FPR1207-F - Technical Manual (18 pages)
- FlexPoint FPR1207-F - Quick Start Guide (2 pages)
- AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual (79 pages)
- AlphaGen CE-3x2 5K-T 48Vdc (95 pages)
- AlphaGen PN-6x-T 7.5kW 48Vdc (95 pages)
- AlphaGen 3.5_5.0kW Kohler COM5 (80 pages)
- Security Bar Field For UPE-3, UPE-6, UPE-M3, UPE-M6, PN Series and CE Series (2 pages)
- 255A Bypass Switch (24 pages)
- AMP24 HP (108 pages)
- FXM350_Micro350 UPS (112 pages)
- CFR 600, CFR 600XT, CFR 1000 (70 pages)
- BPS Series Bypass Switch (36 pages)
- CFR Intelligent Interface Device (54 pages)
- CFR Redundant Control Unit (23 pages)
- CFR 5000, CFR 5000RM (88 pages)
- CFR 3000, CFR 3000RM (86 pages)
- CFR 1500, CFR 1500RM (83 pages)
- CFR 1500, CFR 2000, CFR 2500, CFR 3000 (76 pages)
- Continuity: 1000_2000_3000 (48 pages)
- Continuity Battery Pack (20 pages)
- Continuity: 6K_10K (52 pages)
- Micro, Micro XL, Micro XL3 UPS (99 pages)
- Micro Secure UPS (80 pages)
- Te17 (32 pages)
- Te45 (68 pages)
- Te41, 48V (76 pages)
- Te41, 24V (72 pages)
- Te43 (60 pages)
- AlphaGuard AG-CMT Installation (2 pages)
- AlphaGuard AG-CMT-3SC_4SC-P (2 pages)
- Digital Midtron DM-3200 AT (2 pages)