Doc. #: 026-069-B0 Rev F

52

a. Select Main Menu > Inverters > Group Mapping.

b. Turn the inverter modules OFF by clicking the green power icon at the end of the row. The green

power icons turn black in a few seconds.

c. Match

AC Input Groups

to

AC Output Groups

by configuring the modules to the groups as shown in

Figure 33.

22. DO NOT TURN THE INVERTERS BACK ON. PROCEED WITH THE NEXT STEP.

23. Select

Inverters -> Set Output

to set the number of inverters in each phase of your system. Match the AC

input phase to the corresponding AC output phase.

a. Number of Modules:

Enter the total number of inverter modules that will be installed for that phase.

b. Redundancy:

Enter the number of inverter modules that will provide redundant power for that phase.

This information is used to provide system warnings.

c. Phase Shift

: Enter the phase shift for output group in your system configuration

1

2

3

Split phase (120/240 V)

°

0

180

N/A

2-pole (120/208) °

0

120

N/A

3-phase (120/208 V) °

0

120

240

d. Nominal Output Voltage

: Enter

120

for all phases.

e. Press

Submit

.

CAUTION!

The value entered in the Nominal Output Voltage field can change the actual AC output voltage of the 

inverters. Setting this value to anything other than 120 V will render the UL/CSA approval invalid.

24. Check for alarms (

Inverters > View Live Status

): alarm code (41) PHASE NOT READY indicates that the

phase rotation of the AC Input is not correct. (The inverters will not start until the phase and rotation are

correct.)

If necessary, return to

Inverters -> Set Output

and correct the phases as shown:

Unit 1

Unit 2

Unit 3

2-pole (120/208 V) °

0

240

N/A

3-phase (120/208 V) °

0

240

120

Validating the inverter configuration

For a split phase 120/240V system,

click on heading button 2

For a 3-phase 120/208V system,

click on heading button 3

Figure 33 —

Matching AC Input Groups to AC Output Groups