beautypg.com

5 equipment grounding, 1 safety ground, 2 lightning strike ground – Alpha Technologies AMPS80 HP User Manual

Page 11

background image

9

Doc. #: 026-069-B0 Rev F

1.5 Equipment Grounding

To provide a ready, reliable source of backup power, the power system must be connected to an effective

grounding and earthing system. The grounding system must be designed to protect both personnel and

equipment.

Low impedance grounding is mandatory for personnel safety, critical for the proper opera-

tion of the system, and must be in place and connected to the system before the supply

cables are connected.

1.5.1 Safety Ground

The safety ground is a two-part system – the utility service ground and the power system ground.

Utility Service Ground

As a minimum requirement for the protection of equipment, the local utility service must provide a low-im-

pedance path for fault current return to Earth. This must meet or exceed the requirements of the US National

Electrical Code or the Canadian Electrical Code.

Power System Ground

The power system ground consists of a low-impedance connection between the enclosure and an Earth

Ground, which must be located at least six feet away from the utility earth connection.

1.5.2 Lightning Strike Ground

Lightning strikes, grid switching, or other power surges on the power line and/or communications cable

can cause high-energy transients that can damage the power or communications systems. Without a low-

impedance path to the ground, the current will travel through wires of varying impedance, which can produce

damaging high voltages. The best method to protect the system from damage is to divert these unwanted

high-energy transients along a low-impedance path to the ground.

See section 7.7 for a description of the surge suppression modules installed in the AMPS80 HP.

WARNING!